Description of equipment, Representative piping diagrams – Bell & Gossett DN0130D Domestic Pump 250°F Condensate Units Series SA-PT User Manual

Page 2

Advertising
background image

2

DESCRIPTION OF EQUIPMENT

The Series SA, and SA-P units consists of an ASME Code

stamped steel receiver (permitting operating under pressure up

to 15 psig [1.0 Bar] and equivalent temperature up to 250°F

[121°C]). Series B35 centrifugal pump(s) designed for 2 ft. (0.6M)

NPSH, corrosion inhibitor (anode), water level gauge, ther-

mometer, pressure relief valve, thermostatic air vent trap, com-

pound gauge, valve(s) in pump suction, and a drain (gate)

valve. Occasionally, Series SA units are fully vented; these

receivers feature ASME Code construction except the code

stamped is omitted. In addition to the above components, the

Series SA-P employs a proportioning regulator and valve (elec-

tric or pneumatic). The Series SA unit uses float switch controls.

Control panels and components supplied per specification.
When Series SA units are furnished with ASME Code stamped

receivers, relief valve and air vent trap to permit pressurization,

then the receiver inlet is directly connected to the outlet of the

steam absorption unit or other steam process equipment with-

out steam traps in the return line. When used in this manner, a

separate SA unit is usually required for each independently

controlled heating unit.
It is, however, possible to use a single SA unit with multiple

heating units. Detailed information and drawings will be fur-

nished on request.
The relief valve on the unit is set at 15 psi (1.0 Bar) and rated at

1900 pph (862 Kg/hr) steam. Any additional system protection

must be provided as required by others.
PRELIMINARY INSPECTION
Assure that there is no shipping damage.
Assure that nameplate ratings agree with job specifications and

actual conditions.
HANDLING
Use care in installing unit.

MECHANICAL DRAIN

VALVE (OPTIONAL)

FLOAT SWITCH

FOR STAND BY

THERMOSTATIC

VENT TRAP

TO DRAIN

PUMP

DISCHARGE

DOMESTIC SERIES B35

CENTRIFUGAL PUMP

(SERIES DB PUMP

OPT., SEE DETAIL AA)

GAUGE

GLASS

DIAL

TEMP.

GAUGE

ANODE

COMPOUND GAUGE

PROPORTIONING

REGULATOR

PRESSURE RELIEF VALVE,

PIPE TO DRAIN (PITCH DOWN)

STEAM

ABSORPTION UNIT

OR

CONVERTER

OR

FAN COIL UNIT

OR

STEAM PROCESS

EQUIPMENT

COMPOUND

GAUGE

GAUGE

GLASS

DIAL

TEMP.

GAUGE

DOMESTIC SERIES B35

CENTRIFUGAL PUMP

(SERIES DB PUMP

OPT., SEE DETAIL AA)

PUMP

DISCHARGE

TO DRAIN

ANODE

THERMOSTATIC

VENT TRAP

PRESSURE RELIEF VALVE

PIPE TO DRAIN (PITCH DOWN)

MECHANICAL DRAIN

VALVE (OPTIONAL)

FLOAT SWITCH

PUMP DISCHARGE

FLEXIBLE

PUMP

CONNECTOR

PUMP

SUCTION

LEGEND:

“Y” STRAINER
GATE VALVE
UNION
PLUG COCK
CHECK VALVE
NON SLAM

CHECK VALVE
FLANGE
PROPORTIONING

CONTROL VALVE

DETAIL AA

DETAIL OF RECOMMENDED PIPING TO

SERIES DB HIGH PRESSURE PUMP

1DPD22

1DPD32

High Temperature Condensate Units

Series SA and SA-P

REPRESENTATIVE PIPING DIAGRAMS

SERIES SA

SERIES SA-P

Advertising
This manual is related to the following products: