Bell & Gossett DN0130D Domestic Pump 250°F Condensate Units Series SA-PT User Manual

Page 3

Advertising
background image

LOCATION
Place unit for easy access to all parts. Allow adequate space

for servicing. Check ambient conditions.
NOTICE / TEMPERATURE LIMITS
Motors are designed to operate in 104°F (40°C) max. ambient.

Insulate or ventilate as required.

PIPING (General)
Pipe the unit per the Elementary Piping Diagram. Locate and

support piping so as to not load the pump discharge.
RETURNS
Gravity return lines from system should be properly pitched to

drain to unit by gravity. A “Y” strainer and gate valve should be

installed in the return line.
PIPING (Relief Valve)
The discharge from the relief valve should be piped to a loca-

tion for safe for potential full flow steam. There must also be

provision for drainage of the liquid discharged.

THERMOSTATIC VENT TRAP OR ATMOSPHERIC VENT
Connect piping from drain line, thermostatic vent trap, and

mechanical drain valve (if so equipped) to drain. Occasionally,

Series SA units are furnished fully vented, without thermostatic

vent trap. Oversize vent openings are then supplied; install full

size vent pipe to atmosphere.

FLOAT SWITCHES & MECHANICAL ALTERNATORS
Float switch and/or displacer switches, standard or proportional,

are provided to meet system requirements.
Floats are locked in place to prevent damage during shipment.

Remove shipping locks. Check factory settings. Floats and

mechanical alternators are adjustable for various levels of oper-

ation. The lead pump should start with tank

3

/

4

full and shut off

at 2" (51mm) or more above pump inlet. Lag pump should start

before the tank overflows. Settings should avoid “short

cycling” of the pump.
Displacer positions are adjusted by removing the controller

from the top of the tank and changing cable lengths.
PROPORTIONING ELECTRIC REGULATOR

AND PROPORTIONING (SLIDE WIRE) ELECTRIC VALVE
The regulator is actuated by a float-operated mechanism. Its

function is to regulate the action of the proportioning type of

motor operated valve, so the amount of flow through the valve

is in balance with the water level change.
By accurately following the changes in the water level, the float

actuates a potentiometer slide wire located in the proportioning

regulator. Connected to a similar potentiometer in a relay and

valve operator, the regulator causes the valve to open, close, or

hold in a fixed position.
PNEUMATIC PROPORTIONING

REGULATOR AND CONTROL VALVE
The pneumatic proportional control utilizes controlled air pres-

sure to modulate the discharge valve opening. An air pressure

switch set a 2-3 psi (0.1-0.2 Bar) starts and stops the pump(s)

while the discharge valve is essentially closed.
DISCHARGE CONNECTION – SERIES SA AND SA-P UNITS
A check valve, gate valve and square head steam plug cock

should be located close to pump in discharge line. The plug

cock(s) may be omitted on Series SA-P units equipped with

proportioning discharge valves. If discharge line is more than

100 ft. (30M) long, it should usually be one size larger than the

pump tapping. When the pump is to discharge to a vented

receiver at approximately the same elevation, the steam pres-

sure in the receiver may be greater than the static head at the

pump discharge causing condensate and steam to be forced

through the pump. This condition can be corrected by installing

a back-pressure valve with a spring pressure approximately

equal to the maximum receiver pressure.
ELECTRICAL WIRING & CONTROLS
Connect power wiring per NEC. Recheck nameplate vs. spec-

ifications and conditions. All single phase motors have internal

thermal protection.

3

CAUTION: UNIT LIFTING EYE

Use unit lifting eyes only to lift unit as shipped from

factory. Unit must be empty and disconnected from pipes,

anchors and other restraints. Use proper rigging pro-

cedures. Failure to follow these instructions could result in

injury or property damage.

CAUTION: NOT A CHEMICAL PUMP

Inject boiler feed compounds from chemical feed tank

into boiler feed piping – never into condensate tank. Failure

to follow these instructions could result in injury or property

damage.

WARNING: HIGH VOLTAGE ELECTRICITY

Disconnect and lock out power before connecting or

servicing unit. Failure to follow these instructions could

result in serious injury or death.

WARNING: EXPLOSIBLE

Do not exceed pressure rating of unit (normally 15 psi

[1.0 Bar]). Do not alter or defeat relief valve (must be 15 psi

[1.0 Bar] max.). Pipe relief valve discharge to a safe location.

Failure to follow these instructions could result in serious

injury or death.

WARNING: RELIEF VALVE REQUIRED

For sale operation the system requires a relief valve

set at 15 psi (1.0 Bar) or less. The relief valve discharge must

be piped to a location where 15 psi (1.0 Bar) steam can be

safely discharged. Do not restrict, reduce or valve the relief

valve discharge line. Failure to follow these instructions

could result in serious injury or death.

WARNING: LIMITED PRESSURE RELIEF

VALVE CAPACITY

The pressure relief valve supplied on the unit may not be

sufficient to relieve rated capacity of the unit or full output of

the boiler. Relief valve supplied is rated at 1900 pph (862

Kg/hr) steam. The tank is rated to withstand 125 psi (8.5 Bar),

but the operating pressure must not exceed 15 psi (1.0 Bar).

Professional system design or evaluation, by others, must

evaluate the upstream system and provide for necessary

additional protection. Discharge thru the pressure relief

valve is a symptom of a system failure. The unit must be

valved off immediately. Failure to follow these instructions

could result in serious injury, death or extensive property

damage.

Advertising