Trouble shooting procedures – Bell & Gossett DN0130D Domestic Pump 250°F Condensate Units Series SA-PT User Manual

Page 6

Advertising
background image

1. Hold fittings rigidly to prevent misalignment, which can

cause severe bending stresses in the glass, when packing

nuts are tightened.

2. Provide metal washers so nuts can be tightened without

twisting packing or tube.

3. Provide positive, but not excessive, clearance between

glass, packing nuts, and bearing washers.

4. Keep glass short enough to allow for expansion.
5. Provide positive clearance between the ends of the gage

glass and the metal fittings. Glass-to-metal contact will

keep the gage glass from expanding and cause breakage.

6. Tighten packing nuts enough to prevent leakage, but not so

much that you hinder expansion and contraction. Follow

gage manufacturer’s recommendations.

7. Generally, you can use cylindrical or conical rubber pack-

ings for LOW and MEDIUM pressures. HIGHer pressures

and HIGH temperatures may require specialized packings.

In all cases you should follow the recommendations of the

gage manufacturer.

TROUBLE SHOOTING PROCEDURES

All units are thoroughly tested at the factory before shipment.

They should operate satisfactorily without further adjustment if

properly installed and providing they have not been damaged

by rough handling in transit. If system or unit performance is

not satisfactory, refer to the following check list.
Pump Will Not Start
1. The power supply has been interrupted, disconnect switch

is open, or selector switch is improperly positioned.

2. Incorrect voltage for motor. Check voltage and wiring with

motor characteristics.

3. Incorrect starter coil for power supply.
4. The overload relays the starter have tripped out and must be

reset. Ambient temperature may be too high.

5. Check pump controls or other controls for proper operation.
6. Wiring to control cabinet is incorrect or connections are

loose.

7. The strainer is dirty thus retarding flow. Clean periodically.
Pump Runs Continuously
1. Pump is running backward. Rotation of three phase motors

may be corrected by interchanging any two of the three

wires. Rotation should be clockwise looking down on motor.

2. The total required pressure at the pump discharge is greater

than the pressure for which the pump was designed. Check

the total pressure which includes atmospheric pressure, the

friction head and the static head.

3. A valve in the discharge line is closed or throttled too

tightly. Check valve is installed backwards.

4. The impeller eye is clogged.
5. Pump is too small for system.
Condensate Pump is Noisy
1. The pump is working against a lower pressure than

designed for. While pump is discharging, adjust plug cock in

discharge line until pressure at pump approaches pump

rated pressure.

2. Excessive condensate temperature. Correct system condi-

tions. However, this applies to certain units only; others are

designed to handle boiling water.

3. Magnetic hum or bearing noise in motor. Consult motor

manufacturer’s authorized service station nearest unit

location.

4. Starter chatters. Trouble is caused by low line voltage, poor

connections, defective starter coil, or burned contacts.

5. Pump is running backward.
The System is Noisy
1. Banging in the steam main is usually caused by steam

“imploding” in condensate lying in low points in lines. These

problems can be eliminated by dripping low points, properly

supporting the pipe, or by increasing the pitch of the lines.

2. Improper dripping of the steam mains and risers; where

there is a rise in the steam main, or where it branches off into

a riser, a drip trap must be installed in the drain line.

3. The piping is too small to drain properly.
Steam Flow is Restricted
1. Thermostatic vent not open when cold.
2. Valve closed between vent line and drain or checkvalve

installed backwards.

Relief Valve Discharging
1. Incoming steam pressure exceeds 15 psi (1.0 Bar) –

upstream pressure must not exceed 15 psi (1.0 Bar). Correct

system.

SA-P Pumps Don't Start or Run Continuously
1. If pneumatic system, check pressure setting or pneumatic

pressure switch. Air pressure to engage switch at 2-3 psi

(0.1-0.2 Bar).

2. If electric, check displacer adjustments.

6

Advertising
This manual is related to the following products: