Xylem ADAQCPC Modbus Aquavar CPC User Manual

Page 11

Advertising
background image

11

4XXXX REGISTER MAPPING

DRIVE PARAMETERS

Modbus Ref.

Contents

R/W

Remarks

40002

Reference 1

R/W

Use for Speed Control Macro Only

Range = 0 … 10000 (0 … 100.00%)

40003

Reference 2 (Setpoint)

R/W

Remote Setpoint via Modbus

Range = 0 … 10000 (0 … 100.00%) of Transducer range.

e.g. 0 = 0 psi and 10000 = 300 PSI.

NOTE: Group 16 Setpoint Select must be set to Fieldbus

40005

Actual 1

(Select using 3210)

R

By default, stores nothing. Use parameter 3210 to

select an actual value for this register.

e.g. 3210 = 0101, 40006 = Motor Freq.

40006

Actual 2

(Select using 3211)

R

By default, stores nothing. Use parameter 3211 to

select an actual value for this register.

40007

Actual 3

(Select using 3213)

R

By default, stores nothing. Use parameter 3213 to

select an actual value for this register.

40008

Actual 4

(Select using 3214)

R

By default, stores nothing. Use parameter 3214 to

select an actual value for this register.

40009

Actual 5

(Select using 3214)

R

By default, stores nothing. Use parameter 3215 to

select an actual value for this register.

40010

Actual 6

(Select using 3214)

R

By default, stores nothing. Use parameter 3216 to

select an actual value for this register.

40011

Actual 7

(Select using 3214)

R

By default, stores nothing. Use parameter 3217 to

select an actual value for this register.

40012

Actual 8

(Select using 3214)

R

By default, stores nothing. Use parameter 3218 to

select an actual value for this register.

40031

Aquavar Control Word LSW

R/W

Maps directly to the Least Significant Word of the

Aquavar profile’s CONTROL WORD.

40032

Aquavar Control Word MSW

R

Maps directly to the Most Significant Word of the

Aquavar profile’s CONTROL WORD.

40033

Aquavar Status Word LSW

R

Maps directly to the Least Significant Word of the

Aquavar profile’s STATUS WORD.

40034

Aquavar Status Word MSW

R

Maps directly to the Most Significant Word of the

Aquavar profile’s STATUS WORD.

Group 1

VFD Signal

R/W

Set Value (Dec)

40101

Motor Frequency

R

40102

Motor Current

R

40103

Motor Power

R

40104

DC Bus Voltage

R

40105

Motor Voltage

R

40106

Drive Temp

R

40107

VFD On Time

R

40108

Run Time

R

40109

KWh Counter

R

40110

DI6-1 Status

R

40111

AI1

R

40112

AI2 Trnsdcr Fdbk

R

40113

RO3-1 Status

R

40114

AO1 (mA)

R

40115

AO2 (mA)

R

40116

Last Fault

R

40117

Previous Fault 1

R

40118

Previous Fault 2

R