0XXXX MAPPING MODBUS COILS / AQUAVAR CONTROL WORD

Modbus Ref.

Internal Location

R/W

Command

Value

Notes:

00001

Control Word - Bit 0

R/W

STOP

1 = STOP,

0 = (no op)

STOP Bit Must be

set to 0 to start

drive via Modbus.

If both STOP and

START are set to 1,

drive will stop or
remain stopped.

00002

Control Word - Bit 1

R/W

START

1 = START,

0 = (no op)

00003

Control Word - Bit 2

n/a

Reserved (Not Used)

00004

Control Word - Bit 3

n/a

Reserved (Not Used)

00005

Control Word - Bit 4

R/W

RESET

1 = RESET,

0 = (no op)

00006

Control Word - Bit 5

R/W

EXT2

1 = EXT2,

0 = EXT1

00007

Control Word - Bit 6

n/a

Reserved (Not Used)

00008

Control Word - Bit 7

n/a

Reserved (Not Used)

00009

Control Word - Bit 8

n/a

Reserved (Not Used)

00010

Control Word - Bit 9

n/a

Reserved (Not Used)

00011

Control Word - Bit 10

n/a

Reserved (Not Used)

00012

Control Word - Bit 11

n/a

Reserved (Not Used)

00013

Control Word - Bit 12

n/a

Reserved (Not Used)

00014

Control Word - Bit 13

n/a

Reserved (Not Used)

00015

Control Word - Bit 14

n/a

Reserved (Not Used)

00016

Control Word - Bit 15

n/a

Reserved (Not Used)

00017

Control Word - Bit 16

n/a

Reserved (Not Used)

00018

Control Word - Bit 17

n/a

Reserved (Not Used)

00019

Control Word - Bit 18

n/a

Reserved (Not Used)

00020

Control Word - Bit 19

n/a

Reserved (Not Used)

00021

Control Word - Bit 20

n/a

Reserved (Not Used)

00022

Control Word - Bit 21

n/a

Reserved (Not Used)

00023

Control Word - Bit 22

n/a

Reserved (Not Used)

00024

Control Word - Bit 23

n/a

Reserved (Not Used)

00025

Control Word - Bit 24

n/a

Reserved (Not Used)

00026

Control Word - Bit 25

n/a

Reserved (Not Used)

00027

Control Word - Bit 26

n/a

Reserved (Not Used)

00028

Control Word - Bit 27

n/a

Reserved (Not Used)

00029

Control Word - Bit 28

n/a

Reserved (Not Used)

00030

Control Word - Bit 29

n/a

Reserved (Not Used)

00031

Control Word - Bit 30

n/a

Reserved (Not Used)

00032

Control Word - Bit 31

n/a

Reserved (Not Used)

00033

Not used in CW

R/W

RELAY OUTPUT 1

1 = Energize,

0 = Denergize

00034

Not used in CW

R/W

RELAY OUTPUT 2

1 = Energize,

0 = Denergize

00035

Not used in CW

R/W

RELAY OUTPUT 3

1 = Energize,

0 = Denergize

00036

RESERVED

n/a

Reserved (Not Used)

00037

RESERVED

n/a

Reserved (Not Used)

00038

RESERVED

n/a

Reserved (Not Used)

Supported Function Codes

01 - Read Coil Status

05 - Force Single Coil

15 - Force Multiple Coils (0x0F Hex)