0XXXX MAPPING MODBUS COILS / AQUAVAR CONTROL WORD
Modbus Ref.
Internal Location
R/W
Command
Value
Notes:
00001
Control Word - Bit 0
R/W
STOP
1 = STOP,
0 = (no op)
STOP Bit Must be
set to 0 to start
drive via Modbus.
If both STOP and
START are set to 1,
drive will stop or
remain stopped.
00002
Control Word - Bit 1
R/W
START
1 = START,
0 = (no op)
00003
Control Word - Bit 2
n/a
Reserved (Not Used)
00004
Control Word - Bit 3
n/a
Reserved (Not Used)
00005
Control Word - Bit 4
R/W
RESET
1 = RESET,
0 = (no op)
00006
Control Word - Bit 5
R/W
EXT2
1 = EXT2,
0 = EXT1
00007
Control Word - Bit 6
n/a
Reserved (Not Used)
00008
Control Word - Bit 7
n/a
Reserved (Not Used)
00009
Control Word - Bit 8
n/a
Reserved (Not Used)
00010
Control Word - Bit 9
n/a
Reserved (Not Used)
00011
Control Word - Bit 10
n/a
Reserved (Not Used)
00012
Control Word - Bit 11
n/a
Reserved (Not Used)
00013
Control Word - Bit 12
n/a
Reserved (Not Used)
00014
Control Word - Bit 13
n/a
Reserved (Not Used)
00015
Control Word - Bit 14
n/a
Reserved (Not Used)
00016
Control Word - Bit 15
n/a
Reserved (Not Used)
00017
Control Word - Bit 16
n/a
Reserved (Not Used)
00018
Control Word - Bit 17
n/a
Reserved (Not Used)
00019
Control Word - Bit 18
n/a
Reserved (Not Used)
00020
Control Word - Bit 19
n/a
Reserved (Not Used)
00021
Control Word - Bit 20
n/a
Reserved (Not Used)
00022
Control Word - Bit 21
n/a
Reserved (Not Used)
00023
Control Word - Bit 22
n/a
Reserved (Not Used)
00024
Control Word - Bit 23
n/a
Reserved (Not Used)
00025
Control Word - Bit 24
n/a
Reserved (Not Used)
00026
Control Word - Bit 25
n/a
Reserved (Not Used)
00027
Control Word - Bit 26
n/a
Reserved (Not Used)
00028
Control Word - Bit 27
n/a
Reserved (Not Used)
00029
Control Word - Bit 28
n/a
Reserved (Not Used)
00030
Control Word - Bit 29
n/a
Reserved (Not Used)
00031
Control Word - Bit 30
n/a
Reserved (Not Used)
00032
Control Word - Bit 31
n/a
Reserved (Not Used)
00033
Not used in CW
R/W
RELAY OUTPUT 1
1 = Energize,
0 = Denergize
00034
Not used in CW
R/W
RELAY OUTPUT 2
1 = Energize,
0 = Denergize
00035
Not used in CW
R/W
RELAY OUTPUT 3
1 = Energize,
0 = Denergize
00036
RESERVED
n/a
Reserved (Not Used)
00037
RESERVED
n/a
Reserved (Not Used)
00038
RESERVED
n/a
Reserved (Not Used)
Supported Function Codes
01 - Read Coil Status
05 - Force Single Coil
15 - Force Multiple Coils (0x0F Hex)