Drive parameters – Xylem ADAQCPC Modbus Aquavar CPC User Manual
Page 15
![background image](/manuals/310370/15/background.png)
15
4XXXX REGISTER MAPPING
Group 18
VFD Signal
R/W
Set Value (Dec)
41804
Relay Output 2
R/W
Not Sel [0]
Run [1]
Ready [2]
Fault [3]
Low Water [4]
Pump Prtct [5]
Start Slv [6]
Stand By [7]
Active [8]
41805
RO 2 On Delay
R/W
41806
RO 2 Off Delay
R/W
41807
Relay Output 3
R/W
Not Sel [0]
Run [1]
Ready [2]
Fault [3]
Low Water [4]
Pump Prtct [5]
Start Slv [6]
Stand By [7]
Active [8]
41808
RO 3 On Delay
R/W
41809
RO 3 Off Delay
R/W
Group 19
VFD Signal
R/W
Set Value (Dec)
41901
AO1 Content Sel
R/W
Not Sel [0]
Motor Freq [101]
Motor Curren [102]
Motor Power [103]
Actual [202]
Energy Savin [207]
41902
AO1 Content Min
R/W
41903
AO1 Content Max
R/W
41904
Minimum AO1
R/W
41905
Maximum AO1
R/W
41906
AO2 Content Sel
R/W
Not Sel [0]
Motor Freq [101]
Motor Curren [102]
Motor Power [103]
Actual [202]
Energy Savin [207]
41907
AO2 Content Min
R/W
41908
AO2 Content Max
R/W
41909
Minimum AO2
R/W
41910
Maximum AO2
R/W
DRIVE PARAMETERS