For example, using the standard 300 PSI transducer supplied with the Aquavar CPC:

1. Parameter 1502 (Transducer Max) should be set to 300 PSI.

2. Parameter 1503 (Transducer Min) should be set to 0 PSI.

3. Setting to 60 PSI…

a. 60 PSI / 300 PSI = .2 or 20%
b. Write ‘2000’ to Holding Register 40003

4. Setting to 80 PSI…

a. 80 PSI / 300 PSI = ~.2667 or 26.67%
b. Write ’2667’ to Holding Register 40003

Speed Control through Modbus Interface

1. Set parameter 1102 (Applic Macro) to: [5] Speed Cntrl

2. Configure and Setup Modbus Serial Communications

3. Set parameter 1601 to [0] Setp1

4. Set parameter 1602 to [2] Fieldbus

5. Write a value between ‘10000’ and ‘0’ [100.00% to 0% of Maximum Freq (1401)] to Holding Register 40002.

Note: There is an implied decimal point that is not written between the second (from the right) and third
digit. Thus, 10000 = 100.00%.

For example, using a Maximum Freq of 60 Hz:

1. Parameter 1401 (Maximum Freq) should be set to 60Hz.

2. Parameter 1601 (SP1 / SP2 Select) should be set to 0psi.

3. Parameter 1602 (Set Point 1 Select) should be set to [2] Fieldbus

4. Setting to 60 Hz (Full Speed)…

a. 60 Hz / 60 Hz = 1 or 100%
b. Write ‘10000’ to Holding Register 40002.

Note: Writing to parameter 1403 will have no effect.

5. Setting to 30 Hz (Half Speed)…

a. 30 Hz / 60 Hz = .5 or 50%

b. Write ‘5000’ to Holding Register 40002.

Note: Writing to parameter 1403 will have no effect.