Xylem IM107R06 Wastewater Pumps Dewatering, Effluent and Sewage User Manual

Page 6

Advertising
background image

6

Use the pump H-O-A (Hand-Off-Automatic) switches in

Hand to test the pumps. If they operate well in Hand pro-

ceed to test Automatic operation. If the pumps run but fail

to pump, they are probably air locked, drill the relief holes

per the instructions in the Piping Section.
Place Control Panel switch(es) in Automatic position and

thoroughly test the operation of the ON, OFF, and Alarm

floats by filling the wetwell with clear water. Important:

Failure to provide a Neutral from the power supply to a

1Ø, 230 volt Control Panel will not allow the panel control

circuit to operate. The Neutral is necessary to complete the

115 volt control circuit.
Check voltage and amperage and record the data on the

front of this manual for future reference. Compare the am-

perage readings to the pump nameplate maximum amper-

age. If higher than nameplate amperage investigate cause.

Operating the pump off the curve, i.e. with too little head

or with high or low voltage will increase amperage. The

motor will operate properly with voltage not more than

10% above or below pump nameplate ratings. Performance

within this range will not necessarily be the same as the pub-

lished performance at the exact rated nameplate frequency

and voltage. Correct the problem before proceeding. Three

phase unbalance is also a possible cause. See Three Phase

Power Unbalance and follow the instructions.
Reset the Alarm circuit, place pump switch(es) in the Au-

tomatic position and Control Switch in ON position. The

system is now ready for automatic operation.
Explain the operation of the pumps, controls and alarms to

the end user. Leave the paperwork with the owner or at the

control panel if in a dry, secure location.

FLOAT SWITCH AND PANEL CHART

The purpose of this chart is to show the required switch

quantities and the function of each switch in a typical

wastewater system. The quantities required vary de-

pending on the switch type, single-action or wide-angle.

Switch quantities also vary by panel type: simplex with

and without alarms, and duplex with alarms.
Duplex Panels using single-action switches:
Three Float Panel Wiring
SW1

Bottom

Pumps Off

SW2

Middle

1st Pump On

SW3

Top

2nd Pump & Alarm On

Four Float Panel Wiring ➁
SW1

Bottom

Pumps Off

SW2

2nd

1st Pump On

SW3

3rd

2nd Pump On

SW4

Top

Alarm On

Duplex Panels using wide-angle switches:
Three Float Panel Wiring
SW1

Bottom

1st Pump On/Both Off

SW2

Top

2nd Pump & Alarm On

Four Float Panel Wiring
SW1

Bottom

1st Pump On/Both Off

SW2

Middle

2nd Pump On

SW3

Top

Alarm On

Simplex Panel using single-action switches:
Simplex Panel with Alarm ①
SW1

Bottom

Pump Off

SW2

Middle

Pump On

SW3

Top

Alarm On/Off

Simplex Panel with No Alarm
SW1

Bottom

Pump Off

SW2

Top

Pump On

Inlet

Alarm SW3

Pump On SW2

Pump Off SW1

Discharge

Inlet

Alarm SW4

Lag Pump On

SW3

Pump Off

SW1

Discharge

Lead Pump On

SW2

Simplex ①

Duplex ➁

Simplex Panel using wide-angle switches:
Simplex Panel with Alarm
SW1

Bottom

Pump On/Off

SW2

Top

Alarm On/Off

Simplex Panel with No Alarm
SW1

Pump On/Off