Reset the Alarm circuit, place pump switch(es) in the

Automatic position and Control Switch in ON position.

The system is now ready for automatic operation.

Explain the operation of the pumps, controls and alarms

to the end user. Leave the paperwork with the owner or

at the control panel if in a dry, secure location.

FLOAT SWITCH AND PANEL CHART

The purpose of this chart is to show the required switch

quantities and the function of each switch in a typical

wastewater system. The quantities required vary de-

pending on the switch type, single-action or wide-angle.

Switch quantities also vary by panel type: simplex with

and without alarms, and duplex with alarms.
Duplex Panels using single-action switches:
Three Float Panel Wiring

SW1

Bottom

Pumps Off

SW2

Middle

1st Pump On

SW3

Top

2nd Pump & Alarm On

Four Float Panel Wiring ➁
SW1

Bottom

Pumps Off

SW2

2nd

1st Pump On

SW3

3rd

2nd Pump On

SW4

Top

Alarm On

Duplex Panels using wide-angle switches:
Three Float Panel Wiring
SW1

Bottom

1st Pump On/Both Off

SW2

Top

2nd Pump & Alarm On

Four Float Panel Wiring
SW1

Bottom

1st Pump On/Both Off

SW2

Middle

2nd Pump On

SW3

Top

Alarm On

Simplex Panel using single-action switches:
Simplex Panel with Alarm ①
SW1

Bottom

Pump Off

SW2

Middle

Pump On

SW3

Top

Alarm On/Off

Simplex Panel with No Alarm
SW1

Bottom

Pump Off

SW2

Top

Pump On

Simplex Panel using wide-angle switches:
Simplex Panel with Alarm
SW1

Bottom

Pump On/Off

SW2

Top

Alarm On/Off

Simplex Panel with No Alarm
SW1

Pump On/Off

Inlet

Alarm SW3

Pump On SW2

Pump Off SW1

Discharge

Inlet

Alarm SW4

Lag Pump On

SW3

Pump Off

SW1

Discharge

Lead Pump On

SW2

Simplex ➀

Duplex ➁