INSULATION RESISTANCE READINGS

Normal Ohm and Megohm Values between all leads and ground

Condition of Motor and Leads

Ohm Value

Megohm Value

A new motor (without drop cable).

20,000,000 (or more)

20 (or more)

A used motor which can be reinstalled in well.

10,000,000 (or more)

10 (or more)

Motor in well. Readings are for drop cable plus motor.

New motor.

2,000,000 (or more)

2 (or more)

Motor in good condition.

500,000 - 2,000,000

.5 - 2

Insulation damage, locate and repair.

Less than 500,000

Less than .5

Insulation resistance varies very little with rating. Motors of all HP, voltage and phase ratings have similar values

of insulation resistance.
Insulation resistance values above are based on readings taken with a megohmmeter with a 500V DC output.

Readings may vary using a lower voltage ohmmeter, consult factory if readings are in question.