Xylem IM204 R03 CentriPro 4 Motor User Manual

Page 2

Advertising
background image

2

WARNING

WARNING

WARNING

Important notice: Read safety instructions before proceeding with

any wiring.

All electrical work must be performed

by a qualified technician. Always follow

the National Electrical Code (NEC), or the Canadian

Electrical Code, as well as all local, state and provincial

codes. Code questions should be directed to your local

electrical inspector. Failure to follow electrical codes and

OSHA safety standards may result in personal injury or

equipment damage. Failure to follow manufacturer’s

installation instructions may result in electrical shock, fire

hazard, personal injury or death, damaged equipment,

provide unsatisfactory performance, and may void manu-

facturer’s warranty.

CAUTION

WARNING

WARNING

WARNING

WARNING

WARNING

WARNING

WARNING

DANGER

WARNING

CAUTION

CAUTION

Owner’s Information

Serial #:

Motor #:

Installation Date:

HP:

Phase:

Volts:

Owner’s Information

SAFETY INSTRUCTIONS

TO AVOID SERIOUS OR FATAL PERSONAL INJURY

OR MAJOR PROPERTY DAMAGE, READ AND FOL-

LOW ALL SAFETY INSTRUCTIONS IN MANUAL AND

ON PUMP.
THIS MANUAL IS INTENDED TO ASSIST IN THE IN-

STALLATION AND OPERATION OF THIS UNIT AND

MUST BE KEPT WITH THE PUMP.

This is a SAFETY ALERT SYMBOL.

When you see this symbol on the pump or

in the manual, look for one of the fol-

lowing signal words and be alert to the

potential for personal injury or property

damage.
Warns of hazards that WILL cause serious

personal injury, death or major property

damage.
Warns of hazards that CAN cause serious

personal injury, death or major property

damage.
Warns of hazards that CAN cause personal

injury or property damage.

NOTICE: INDICATES SPECIAL INSTRUCTIONS

WHICH ARE VERY IMPORTANT AND MUST BE

FOLLOWED.
THOROUGHLY REVIEW ALL INSTRUCTIONS

AND WARNINGS PRIOR TO PERFORMING ANY

WORK ON THIS PUMP.
MAINTAIN ALL SAFETY DECALS.

DANGER

CAUTION

WARNING

USE THIS INFORMATION IN ADDITION TO THE PUMP INSTALLATION DATA

PROVIDED BY PUMP MANUFACTURER.

CentriPro motors are not designed for use

in swimming pools, open bodies of water,

hazardous liquids, or where flammable gases exist. Well

must be vented per local codes.

Disconnect and lockout electrical power

before installing or servicing any electrical

equipment. Many mtors are equipped with automatic

thermal overload protection which may allow an over-

heated motor to restart unexpectedly.

All three phase (3Ø) controls for sub-

mersible motors must provide Class 10,

quick-trip, overload protection.

Do not lift, carry or hang motor by the

electrical cables. Damage to the Electri-

cal Cables can cause shock, burns or death.

Use only stranded copper wire to pump/

motor and ground. The ground wire

must be at least as large as the power supply wires. Wires

should be color coded for ease of maintenance and

troubleshooting.

Install wire and ground according to the

National Electrical Code (NEC), or the

Canadian Electrical Code, as well as all local, state and

provincial codes.

Install an all leg disconnect switch where

required by code.
The electrical supply voltage and phase

must match all equipment requirements.

Incorrect voltage or phase can cause fire, motor and

control damage, and voids the warranty.

All splices must be waterproof. If using

splice kits follow manufacturer’s instruc-

tions.

Select the correct type and NEMA grade

junction box for the application and

location. The junction box must insure dry, safe wiring

connections.

Failure to permanently ground the pump,

motor and controls before connecting to

power can cause shock, burns or death.

4" motors ≥ 2 HP require a minimum

flow rate of .25 ft/sec. or 7.62 cm/sec. past

the motor for proper motor cooling. The following are

the minimum flows in GPM per well diameter required

for cooling: 1.2 GPM/4", 7 GPM/5", 13 GPM/6", 20

GPM/7", 30 GPM/8" or 50 GPM in a 10" well. Pumps
≥ 2 HP installed in large tanks should be installed in a

flow inducer sleeve to create the needed cooling flow or

velocity past the motor.

All motors require a minimum 5'

submergence for proper refill check valve

operation.

This motor has been evaluated for use

with Water Only.