Aquavar ABII

Quick Start Up Guide

LABELS FOUND ON THE CONTROLLER ACCESS COVER:

Fault Codes

Motor Overload Setting

WARNING: Disconnect Power And Wait For LED Indicator To

Turn Off Before Touching Motor Overload Setting Switches.

1 = UP 0 = DOWN

DIP Switch Setting Motor Overload Setting (Amps)

1 2 3 4

1AB2

2AB2

1 1 1 1

2.5

4.6

1 1 1 0

2.8

5.2

1 1 0 1

3.3

5.3

1 0 1 1

3.5

5.8

0 1 1 1

3.8

6.5

0 0 0 0

4.2

6.9

Status Codes*

Green Light Codes

Constant Standby/Low Voltage
Blinking Pump Running

Red Light Codes

Constant Replace Controller
1 Blink

No Water/Loss Of Prime

2 Blinks

Tank Water-Logged

3 Blinks

Pressure Sensor Fault

4 Blinks

Pump or Motor Bound

5 Blinks

Short Circuit

6 Blinks

Ground Fault

7 Blinks

High Temperature

8 Blinks

Over Voltage (>264V)

9 Blinks

Motor Overload

*No Light - No/Very Low Voltage

Motor Overload Setting Label

Use this label to choose the correct Motor Overload Switch

Setting. This label is found under the controller access cover.

Status Code Label

Use this label to diagnose any system errors. This label is

found on the side of the controller access cover.

Application Switch Setting

WARNING: Disconnect Power And Wait For LED Indicator To Turn

Off Before Touching Application Setting Switches.

DIP Switch Setting

1 = UP 0 = DOWN

1 2 3 4

Minimum Speed (Hz)

Ramp Setting

1 1 1 1 *

10

Slow

1 1 1 0 *

10

Medium

1 1 0 1 *

10

Fast

1 0 1 1

30

Slow

0 1 1 1

30

Medium

0 0 0 0

30

Fast

*THESE SETTINGS ARE NOT TO BE USED WITH SUBMERSIBLE PUMPS.

Application

Switch

Setting

Label
Use this label
to choose
the correct
Application
Switch Setting.
This label is
found under
the controller
access cover.

QUICK START GUIDE

IMS-ABII-2