SeRIOUS PeRSOnAL InJURY, DeAtH AnD/OR

PROPeRtY DAMAGe.

The pressure switch is piped into the suction line. There

is an adjusting dial located inside of the control. This

adjustment controls the low suction cutout.
The differential pressure setting is fixed at 1.5 PSI.

Therefore cut in pressure will be the switch setting plus

1.5 PSI.
Although the scale is calibrated in PSI, it may not cor-

respond exactly to the actual suction gage indication.

Therefore, for critical installations, the setting should be

adjusted according to the gage reading.
The approximate settings should be set prior to placing

the unit in operation to suit the pressure conditions at

the installation.

System Pressure Switch (Simplex), Pump 1 and

Pump 2 Pressure Switch for Duplex

ELECTRICAL SHOCK HAZARD. DIS-

CONNECT AND LOCKOUT POWER

BEFORE SERVICING THE UNIT. FAILURe tO FOL-

LOW tHeSe InStRUctIOnS cOULD ReSULt In

SeRIOUS PeRSOnAL InJURY, DeAtH AnD/OR

PROPeRtY DAMAGe.

This switch is piped to the discharge header piping.

There are two adjusting screws located on the top of the

control. Facing the switch, the screw on the right hand

side sets the cut-out point. This adjustment must be made

first.
The screw to the left and towards the front sets the cut-

in point. Turn the screw until the proper cut-in point is

obtained.
Although the scales are calibrated in PSI, they may not

correspond exactly to the actual discharge gage indica-

tion. Therefore, for critical installations, the settings

should be adjusted according to the gage reading. See

wiring diagram 1SWD0 for proper settings of the sys-

tem pressure switches on a duplex unit.

Minimum Run Timer
For a simplex unit the minimum run timer is factory set

to 5 minutes. The setting should be verified before unit is

place into operation and adjusted if a shorter minimum

run time is desired. See Appendix 1 for instructions on

using the programmable pump sequence control module

to set the minimum run timers for a duplex unit. Appen-

dix 1 also contains information about setting additional

parameters that are specific to duplex units.

Aquastat
The aquastat for high temperature cut out is factory set

for 100° F and should be adjusted if a different cut out

temperature is desired. The switch should not be set

above 5° F.

Optional Tank
Since a variety of different tanks can be used with either

the simplex or duplex units refer to the specific IOM that

was shipped with the tank for installation and operating

instructions.

SectIOn 3

pUTTING THE UNIT INTO SERVICE

PREVENT SUBSEQUENT DAMAGE.

A UNIT SHOWING SYMPTOMS OF

POSSIBLE PROBLEMS (NOISE, LEAKS, VIBRATION,

AND/OR CONTINUAL OPERATION) MUST BE COR-

RECTED IMMEDIATELY. FAILURe tO FOLLOW

tHeSe InStRUctIOnS cOULD ReSULt In PROP-

eRtY DAMAGe AnD/OR MODeRAte PeRSOnAL

InJURY.

Simplex package - for capacities up to 110 GPM.
Whenever the city water pressure falls below the system

pressure switch setting the pump will start through a

power relay.
When the system pressure rises above the setting of the

system pressure switch the pump will stop (provided the

minimum run timer has expired.)
Duplex package - for capacities up to 0 GPM.
The lead pump operates identically to the Simplex pack-

age. However, if the draw rate continues to increase be-

yond the capacity of the lead pump, the system pressure

will fall and cause Pump  On/Off pressure switch to trip

which in turn starts the lag pump.
Both pumps will continue to run until the system pres-

sure rises above the setting of Pump 1 and Pump  pres-

sure switches (provided the minimum run timers have

expired.)
For the duplex unit Pump  also acts as a Standby for

Pump 1. In the event there is a call for Pump 1 and it has

failed for whatever reason, Pump  will start and act as

the lead pump. Once Pump 1 is fixed, place the Pump 1

HOA into the Off/Reset position and then back to Auto

to reset the unit.
Simplex and Duplex units will run when there is demand

unless one of the following conditions occurs:

1) The optional low suction pressure switch trips due

to low city pressure

) The high temperature cut out switch trips due to

the pump deadheading.

The low suction condition will reset automatically

when city pressure returns to an acceptable level.
If the unit cuts out on high temperature the unit can

reset automatically when there is demand by drawing

cooler water throughout the unit and across the tem-

perature sensor. This will cool the sensor and cause

it to change state and restart the pump. A manual

purge can be done by running the unit in "Hand" for

about 5 seconds. The unit can then be put back into

"Auto" for normal operation.

AdJUSTmENTS ANd SETTINGS

Low Suction Pressure Switch (Optional)

ELECTRICAL SHOCK HAZARD.

SINGLE PHASE OR THREE PHASE AC

POWER. DISCONNECT AND LOCKOUT POWER

BEFORE SERVICING THE UNIT. FAILURe tO FOL-

LOW tHeSe InStRUctIOnS cOULD ReSULt In

CAUTION

WARNING

WARNING