10) With starter pulled in, check voltage at bottom of

overload block. Voltage should be the same as the

incoming power. If no voltage is present, replace

the starter. If voltage is present, contact electrician

to check the leads and motor.

PUMP WILL nOt BUILD PReSSURe:

1) Check rotation; rotation should be as indicated on

the pump volute. If rotation is wrong disconnect

power. For three phase motors, switch any two

leads at bottom of starter. If motor is single phase,

refer to wiring diagram on nameplate.

HIGH VOLTAGE  PHASE POWER

CAN KILL. DISCONNECT AND LOCK-

OUT POWER PRIOR TO SERVICING UNIT. FAILURe

tO FOLLOW tHeSe InStRUctIOnS WILL ReSULt

In SeRIOUS PeRSOnAL InJURY, DeAtH AnD/OR

PROPeRtY DAMAGe.

) Suction valve is closed. If closed, open.
) Motor not operating at rated RPM. Have motor

checked at local motor repair shop.

) Internal pump damage. Take pump to authorized

pump repair facility.

PUMP WILL nOt StARt AUtOMAtIcALLY:

ELECTRICAL SHOCK HAZARD.

INSPECT ALL ELECTRICAL CONNEC-

TIONS PRIOR TO POWERING THE UNIT. WIRING

CONNECTIONS MUST BE MADE BY A QUALIFIED

ELECTRICIAN IN ACCORDANCE WITH ALL APPLI-

CABLE CODES, ORDINANCES AND GOOD PRAC-

TICES. FAILURe tO FOLLOW tHeSe InStRUc-

tIOnS cOULD ReSULt In SeRIOUS PeRSOnAL

InJURY, DeAtH AnD/OR PROPeRtY DAMAGe.

1) No power. Restore if there is no power.
) No control circuit. Restore control circuit power.
) HOA switch not in the AUTO position. Turn

switch to AUTO position.

) System pressure (Simplex) or Pump 1 and Pump 

(Duplex) pressure switches not adjusted properly.