Installation and operation manual moh1, Starting of operation without given values – Xylem MOH1 Single or dual zone mixing module (obsolete) User Manual

Page 12

Advertising
background image

1

Installation and operation manual MOH1

www.lainginc.com

Starting of operation without given values

1. Remove protection cap / or thermostatic head / or electric drive from

the MOH1 (see page 8 picture 1).

. Increase the supply temperature from the radiator-/boiler circuit to the

designed value (normally 131-140°F).

3. To perform the adjustment check, the room temperature has to be

at least 68°F. If it is not, the system has to be run until the temperature

increases.

4. Check the floor heating supply temperature. It should be about

95-104°F. If it is too high, the flow from the primary supply has to be

adjusted (reduced), see page 8 picture 3.

The MOH1 will be delivered from factory with fully opened mixing

valve. We recommend an adjustment in small steps (1/ turn). After

each adjustment the floor heating supply temperature should be

checked after an appropriate waiting period.