Installation and operation manual moh1 – Xylem MOH1 Single or dual zone mixing module (obsolete) User Manual
Page 13
13
Installation and operation manual MOH1
www.lainginc.com
Starting of operation with given values (pre-setting)
E.g.
Given values:
Heat requirement of underfloor heating system
2000 Watt.
Supply temperature of radiator-/boiler system
158°F.
Return temperature of underfloor heating system
104°F
therefore: dT of 104°F to 158°F = 10 Kelvin
Difference pressure of the radiator-/boiler circuit
1.45 PSI
Specific heat capacity of water
1,163
W
/
(Kg x K)
Wanted values:
Flow from the radiator-/boiler circuit =
m = Q/(c x dT) = 000 W / (1,163
W
/
(kg x K)
x 30 K) = 58 l/h
Pre-setting:
If the difference pressure from the radiator-/boiler circuit at the inlet and
outlet of the MOH1 is 1.45 PSI and the flow requirement of the MOH1 is
about 60 l, the mixing valve pre-setting has been opened by 1,6 turns.
Turns to open
N