Installation and operation manual MOH1

www.lainginc.com

Starting of operation with given values (pre-setting)

E.g.

Given values:

Heat requirement of underfloor heating system

2000 Watt.

Supply temperature of radiator-/boiler system

158°F.

Return temperature of underfloor heating system

104°F

therefore: dT of 104°F to 158°F = 10 Kelvin

Difference pressure of the radiator-/boiler circuit

1.45 PSI

Specific heat capacity of water

1,163

W

/

(Kg x K)

Wanted values:

Flow from the radiator-/boiler circuit =

m = Q/(c x dT) = 000 W / (1,163

W

/

(kg x K)

x 30 K) = 58 l/h

Pre-setting:

If the difference pressure from the radiator-/boiler circuit at the inlet and

outlet of the MOH1 is 1.45 PSI and the flow requirement of the MOH1 is

about 60 l, the mixing valve pre-setting has been opened by 1,6 turns.

Turns to open

N