Installation and operation manual MOH1

www.lainginc.com

Application

• The MOH1 is designed to supply floor heating areas up to approx.

400 Sq. Ft. (from pipe 16x mm onwards) in one- or two-pipe-systems.

The connection of up to 2 floor heating circuits is possible.

• Three versions are available:

MOH1 KF: Mixing set with room temperature guided control, made

of thermostat (50-79°F + frost protection)

with remote sensor (16 Ft.).

MOH1 RT: Mixing set for temperature guided control, made of

thermoelectric drive for the connection of a room

thermostat (room thermostat not included in delivery-

see accessories in product range).

MOH1 KR: Mixing set with integrated constant temperature control

(68-158°F) for the connection of a room thermostat

(room thermostat not included in delivery-

see accessories in product range).

• The MOH1 is provided with a temperature protection system that

restricts the supply temperature in the floor heating circuit to max.

131°F.

Mounting instructions

• MOH1 will be connected directly to the existing radiator-/boiler circuit.

• When two circuits are connected to the MOH1, the shortest circuit

must be balanced by using an adjustable return screw connection.

• The MOH1 must be mounted in a horizontal position (see page ).

Left or right connection to the radiator-/boiler circuit is possible

(see page 9).

• The MOH1 has to be installed on a higher level than the floor heating

installation.

• Ensure that the pre-pressure to the MOH1 from the radiator-/vessel

circuit is minimum 1.45 PSI

• Before running the MOH1 please check, that the floor heating system

is filled, completely vented, and proved against leakage.