Xylem MM 217K Series 150S and 157S Low Water Cut-Offs/Pump Controllers User Manual

Page 3

Advertising
background image

3

Approximate

Distance Above

Cast Line

Differential

Setting

In. (mm)

In. (mm)

Motorized

15

/

16

(24)

Valve Closed

5

/

16

(8)

Motorized

5

/

8

(16)

Valve Open

Burner On

5

/

8

(16)

3

/

8

(16)

Burner Off

1

/

4

(6.4)

Motorized

1

3

/

8

(41)

3

/

4

(19)

Valve Closed
Motorized

5

/

8

(16)

Valve Open

Burner On

7

/

8

(22)

7

/

8

(22)

Burner Off

0

(0)

Values are ± 8” (3.2mm).

NOTE: Due to the slower operation of some
motorized valves, complete valve opening
or closing will occur at slightly different
levels than indicated above.

Model 158S

150 psi (10.5 kg/cm

2

) Levels

0 psi

(0 kg/

cm

2

)

150 psi

(10.5 kg/

cm

2

)

Pressure

Settings and Differential Pressures (continued)

150 psi

(10.5 kg/

cm

2

)

Approximate

Distance Above

Cast Line

Differential

Setting

In. (mm)

In. (mm)

Pump Off

15

/

16

(24)

3

/

8

(16)

Pump On

9

/

16

(14)

Burner Off

0

(0)

N/A

Pump Off

1

7

/

16

(37)

3

/

4

(19)

Pump On

11

/

16

(17)

Burner Off

-

3

/

8

(-16)

N/A

Model 158S-MD

0 psi

(0 kg/

cm

2

)

Pressure

150 psi (10.5 kg/cm

2

) Levels

NOTE: Due to the slower operation of some
motorized valves, complete valve opening
or closing will occur at slightly different
levels than indicated above.

BURNER OFF

BURNER ON

7

/

8

"

DIFFERENTIAL

(22mm)

MOTORIZED

VALVE

CLOSED

BURNER

OFF

NORMAL BOILER

WATER LINE

1

3

/

8

"

DIFFERENTIAL

(35mm)

MOTORIZED

VALVE

CLOSED

MOTORIZED

VALVE

OPEN

3

/

4

"

DIFFERENTIAL

(19mm)

MOTORIZED

VALVE

OPEN

CLOSED

3

/

4

"

DIFFERENTIAL

(19mm)

MOTORIZED

VALVE

CLOSED

BURNER

OFF

NORMAL BOILER

WATER LINE

1

13

/

16

"

DIFFERENTIAL

(46mm)