9

WIRING DIAGRAMS

For Motorized Valves, refer to the valve manufacturer's wiring instructions.

Low Water Cut-Off Only

1. Main Line Switch - For burner circuits within the

switch’s electrical rating.

1. Main Line Switch - For burner circuits within

the switch’s electrical rating.

2. Pilot Switch - To holding coil of a starter when

the burner circuit exceeds the switch’s electrical
rating.

LINE

LOAD

1 2

4 5 6

1 2

4 5 6

ALARM

NEUTRAL

HOT

ALARM

NEUTRAL

HOT

1 2

4 5 6

1 2

4 5 6

SEE PUMP

CONTROL

CIRCUIT

TO NEUTRAL

TO BURNER CONTROL CIRCUIT

HOT

ALARM

1 2

4 5 6

LOAD

LINE (3 PHASE)

SEE PUMP

CONTROL

CIRCUIT

ALARM

1 2

4 5 6

LOAD

LINE

1 2

4 5 6

LOAD

LINE

OR

OR

OR

Combination Pump Control, Low Water Cut-Off and Alarm

Alarm Circuit Only

1. Low Water Alarm

2. High Water Alarm

2. Pilot Switch - To holding coil of a starter when

the burner circuit exceeds the switch’s electrical
rating.

Pump Control Only

1. Install a starter or relay in pump control circuit,

as shown, to prevent damage to snap switch
and help insure proper switch/control operation.
Failure to do so may shorten the life of the
switch when actual amperage exceeds
switch rating.

2. Connect wires from holding coil of pump starter

or relay to terminals 1 and 2 as shown.

NOTE: To help insure most effective operation,
balance boiler feed pump(s) to deliver required water
feeder rate to match boiler steaming requirements.

NOTE: For Model 159S, use terminals 5 and 6 from
starter or relay for pump # 2.