STEP 4 - Electrical Wiring

• To prevent a fire, do not use this product to switch currents over 7.4A, 1/3 Hp at 120 VAC or 3.7A, 1/3 Hp at 240

VAC, unless a starter or relay is used in conjunction with it.

• To prevent electrical shock, turn off the electrical power before making electrical connections.
• This low water cut-off must be installed in series with all other limit and operating controls installed on the

boiler. After installation, check for proper operation of all of the limit and operating controls, before leaving

the site.

• Modification of the switch assembly before or after installation could cause damage to the boiler and/or

boiler system.
Failure to follow this warning could cause electrical shock, an explosion and/or a fire, which could result in
property damage, personal injury or death.

!

WARNING

Switch Operation

For all Models except 158S and 159S

For Model 158S

Boiler feed pump off,

burner on, alarm off.

Boiler feed pump on,

burner on, alarm off.

Boiler feed pump on,

burner off, alarm on.

1

2

4

5

6

1

2

4

5

6

1

2

4

5

6

Motorized valve closed,

burner on, alarm off.

Motorized valve open,

burner on, alarm off.

Motorized valve open,

burner off, alarm on.

4

5

6

1

2

3

4

5

1

2

3

4

5

1

2

3

6 6

For Model 159S

Pump #1 off,

pump #2 off.

Pump #1 on,

pump #2 off.

Pump #1 on,

pump #2 on.

1

2

5

6

1

2

5

6

1

2

5

6

K

a. Using a flathead screwdriver, remove the

junction box cover (K).

7