Determine the seal size – Xylem P81547D Series 90 In-Line Centrifugal Pump User Manual

Page 20

Advertising
background image

WARNING:
Make certain that the internal pressure is relieved before you continue.
Failure to follow these instructions can result in serious personal injury
and/or property damage.

11. Remove the volute capscrews and remove the pump assembly from the volute.

Determine the seal size

All seals, except the 1.25 in. (3.16 cm), require a spring retainer as part of the seal
assembly.
1. Determine if you have an A or AA-type pump using these diagrams and refer to these

diagrams whenever seal replacement becomes necessary.
The primary feature that distinguishes the A from the AA-type pumps is size. Most
components of the A and AA pump seals are similar, but not interchangeable.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

1. Shaft

8. Volute

2. Slinger

9. Impeller capscrew

3. Bracket coverplate

10. Gauge tapping

4. Volute capscrew

11. Suction

5. Discharge

12. Volute gasket

6. Companion flange

13. Seal assembly

Maintenance

Series 90 Installation, Operation, and Maintenance Manual

19