SERVICE INSTRUCTIONS

(Follow these first three steps for all VSC(S) pumps, then pro-

ceed to the pump size and model that corresponds to the size

and model on the pump nameplate).

1. Close valves on suction and discharge sides of pump. If

no valves have been installed, it will be necessary to drain

the system.

2. Remove the coupler guard. Refer to section titled “Hex

Coupler Guard Removal/Installation.”

3. Loosen the capscrews which secure the coupler flanges to

the coupler hubs. Remove the coupler flanges and sleeve

by compressing the flanges and pulling out from beneath

the hubs or by loosening the allen set screws and sliding

the hubs back on the shafts. Remove the coupler hub from

the pump shaft.

6

WARNING: Unexpected Startup Hazard

Disconnect and lockout power before servicing.

Failure to follow these instructions could result in serious

personal injury or death, or property damage.

CAUTION: Extreme Temperature Hazard

Allow pump temperatures to reach acceptable levels

before proceeding. Open drain valve, do not proceed until

liquid stops coming out of drain valve. If liquid does not

stop flowing from drain valve, isolation valves are not seal-

ing and should be repaired before proceeding. After liquid

stops flowing from drain valve, leave valve open and con-

tinue. Remove the drain plug located on the bottom of the

pump housing. Do not reinstall plug or close drain valve

until reassembly is completed. Failure to follow these

instructions could result in property damage and/or moder-

ate personal injury.