Seal type

Parameter

Value

Flushed double seals

1,3,4

pH range limits

pH 7–9

Liquid temperature range

0˚F to 250˚F (-18˚C to 121˚C)

Packing

2

pH range

pH 7–9

Liquid temperature range

0˚F to 200˚F (-18˚C to 93˚C)

Table notes

1. An external flush is required on low pressure systems that contain a high

concentration of abrasives.

2. Use packing on open or closed systems which require a large amount of makeup

water, as well as systems that are subjected to a wide variety of chemical conditions
and solids buildup.

3. For operating temperatures above 250°F, a cooled flush is required and is

recommended for temperatures above 225°F for optimum seal life. On closed
systems, cooling is accomplished by inserting a small heat exchanger in the flush line
to cool the seal flushing fluid.

4. Flush-line filters and sediment separators are available on request.

Product Description

12

Series 1510 Installation, Operation, and Maintenance Manual