MICRO-FLO

Page 6

5.0 Installation
5.1 Wiring Connections

On sensor mounted units, the output signal
wires must be installed through the back panel
using a second liquid-tite connector (included).
To install the connector, remove the circular
knock-out. Trim the edge if required. Install the
extra liquid-tite connector.

On panel or wall mounted units, wiring may be
installed through the enclosure bottom or
through the back panel. See below.

KNOCK-OUT ½” diameter

Power Input

CIRCUIT

BOARD

Power input (+ 9-28 Vdc)
Power input ( ground )
Sensor input (+) RED
Sensor input (signal) BARE
Sensor input ( - ) BLACK

Programming disable jumper (un-installed).
Install on both pins to disable programming.

Front panel touch pad
ribbon cable connection

(+)

(+)

Rear view

(-)

(-)

Alarm output

Open Collector
30 VDC max
50mA max

Pulse output

Digital sq. Wave
5 VDC high
<.25 VDC low
50% duty cycle

5.3 Flow Verification Output Signal

When connected to external equipment such as a PLC, data logger, or Blue-
White metering pump, the pulse output signal can be used as a flow verification
signal. When used with Blue-White metering pumps, connect the positive (+)
terminal on the Micro-Flow circuit board to the pump’s yellow signal input wire
and the negative (-) terminal to the black input wire.

5.2 Circuit Board Connections