OM−04417

SM SERIES

PAGE B − 15

INSTALLATION

Motor Cable Grounding Test

Do not connect the pump control cable
to the control box or incoming voltage
before verifying the pump ground;
otherwise, personnel will be exposed to
serious injury or death.

Using a volt-ohm meter, connect one lead to the
motor cable green/yellow ground lead. Connect
the other lead to an uninsulated point on the pump
body. The test circuit should close.

If the test circuit does not close, there is a defect in
the cable or motor which must be corrected.

Control Box Connections

This pump is shipped completely wired for the volt-
age shown on the nameplate, and is ready for op-
eration through an approved control box.

Ground and wire the control box in accordance
with the instructions accompanying it.

NOTE

For reference, internal motor wiring connections
are shown in the Maintenance and Repair manual.