Firmware Tab

The Firmware Tab is where software revision upgrades

will be located. Clicking on the Firmware Tab will show the

following information:

Module Type: Shows the modules located in the console

that you are connected to. The information here will differ

depending on the configuration of the particular console

you are connected to (The Colibri console will only show

the Controller Module).
• A green button next to Module Type indicates that this

module currently has the latest version of software

installed.

• A red button next to the Module Type indicates that this

module does NOT currently have the latest version of

software installed. This can be verified by comparing the

Current Version with the Available Version numbers.

Slot: Is the physical location of the module in the console.
Current Version: Shows the version that is currently on

the module in the console that you are connected to.
Available Version: Lists the latest released versions of

software available to upgrade the software on the console.

Upgrading Firmware Steps

Assume as an example we want to upgrade the 4-20mA

Input Module. The console currently shows version 0.9.4

installed and version 0.9.8 is available.
Select the Upgrade Selected button after highlighting the

specific module to be upgraded.
For the example we would highlight the 4-20mA Input

Module and click the upgrade selected button. You will be

prompted with this warning.

Make sure historical data is saved. Then click OK. This will

bring up the confirmation screen.

Notice the Estimated time to complete, do not restart your

computer or console without allowing enough time for the

upgrade to complete.
Click OK to continue the upgrade process.
The bottom of the TSA Upgrade tool will show the status of

the upgrade process. There are three steps in the upgrade

process:
• “Upgrading (module name) Module” is the first step and

will take the most time

• “Rebooting” is the second step in the upgrade process.

This step is rebooting the console.

• “Ready” is an indication that the console has been

upgraded and rebooted and has returned to normal

operation.

Important Notes

:

• We recommend that each module be upgraded

individually. Do not use the Upgrade All Button.

• Upgrade the Controller Module first and then the

Power Supply Module second, followed by the

remaining modules.

DTU Tab

The DTU tab is used for logging DTU signal quality only.

The output for the data log will be posted in a different

folder for each specific Controller Serial Number

under \ My Document \ TSA Upgrade

Tool with a filename of DTU Status Log.