Recovering a Module (T5 Series Gauge Only)

If one or more of the modules indicates a flashing “run” light during an upgrade the recovery steps below should be used

to recover the module.
IMPORTANT NOTE:

If more than one module has the flashing “green” run light, power down the console and remove all but one of the modules.

Power the console back up and recover them one at a time. Modules should not be re-inserted with power supplied, power

down the unit each time modules are added. The recover program will not find multiple modules to recover.
If there are multiple modules flashing green, then all of the offending modules, with the exclusion of one, need to be

removed. The one remaining offending module can then be recovered via the following methods. Afterwards reinstall each

module one by one recovering each in turn.
You will need to type in “recover” in the address bar after the 2

nd

forward slash

Ex.

http://ip address/recover

This will recover the module that has been lost during an upgrade. Recover screen is shown below.

1. Click the browse button.

2. Open the software version folder labeled T5Sxx (xx = software version).
3. Open up the Firmware folder