Franklin Fueling Systems Memory Backup Battery for Tank Sentinel, AutoStik, & BulkStik ATGs User Manual

Replacement part instructions

Advertising
background image

www.franklinfueling.com

PN & Rev: 0000210C

E - m a i l : t e c h @ f r a n k l i n f u e l i n g . c o m

F A X 1 - 2 0 7 - 2 8 2 - 9 0 0 2

T E L 1 - 8 0 0 - 9 8 4 - 6 2 6 6 P AG E

1 o f

2

s a l e s @ f r a n k l i n f u e l i n g . c o m

F A X 1 - 2 0 7 - 2 8 3 - 0 1 5 8 T E L 1 - 8 0 0 - 8 7 2 - 3 4 5 5

REPLACEMENT

PART

INSTRUCTIONS

Memory Backup Battery Replacement Instructions

for Tank Sentinel, AutoStik, & BulkStik ATGs

Parts & Materials
Required:

One new 3 volt lithium
battery (INCON P/N:
TSSP-BAT / 390-0004), a
thin piece of adhesive tape,
and a digital multimeter with
test probes.

Diagram:

Testing the
Battery ( B1 )

Use a digital multimeter set
to read 5 DC volts and
measure the DC voltage
between the + battery
terminal and ground or
the yellow-colored metal
shield
(+2.8 to +3.3 volts DC is good).

When to Test the

Battery Voltage (Schedule)

: Yearly after the first two years of operation or use.

DANGER Electrical Shock Hazard.

Make sure all safety shields are installed to

prevent electrical shocks — DO NOT touch any device other than the battery.

Removal & Installation Steps

( with Tank Gauge Power ON & SW 1 ON ):

1.) Printout the complete system and tank setup reports for all tanks. (

Note

– if the

power goes out or is turned off while the battery is out of its holder then all of the
setup/programmed values of the system will be lost. If this happens then the entire
tank gauge will have to be reprogrammed ).

WEDGE UP HERE

ABOUT 1/8 INCH

Battery Cutaway

Side View

b

PRY OUT HERE

a

Yellow

colored

metal

shield

b

TS-1001/N-N U10

VER No. DATE

a

Replace the battery if the voltage reading is below

2.8 volts DC

Advertising