Installation, continued

1.6 Status LEDs

The status LEDs are located on the front panel

of the unit. Normal operation is indicated by

the green LED ON, and the red LED OFF. LED

status indication also has a time delay when

reporting failures. The time delay is similar to

that illustrated in Section 1.5.

1.7 AC Input Power Connection

The Flexnet 300 offers switchable

AC input power capability. Slide

the input power switch (located

on the side of the housing) to the

correct voltage and plug the AC

power cord into the receptacle.
Verify that the green LED is

continuously illuminated and the

red LED begins to blink within

20 seconds, indicating that the

battery pack is not yet installed.

_
+

1.8 Battery Connection

Using a multimeter, verify that 48Vdc is present at the connection

leading from the battery pack, and the polarity is correct. Connect the

battery pack to the Battery connection on the front of the unit. Note the

shape of the Battery connectors which prevent incorrect hookup. Verify

that the red alarm LED goes out within 10 seconds.