Installation, continued

1.9 Output Distribution Board (optional)

The Output Distribution Board (Alpha P/N 745-577-20) splits the ELPM300-48D’s 300W

output into two 150W isolated outputs. Each output has its independent protection circuit.

One output overload or short circuit will only trigger its own protection and not affect the other

circuit’s normal operation.
The ODB measures 6.25” W x 3.875” H x 2” D (159mm W x 98.4mm H x 51mm D).

The adapter bracket mounts to the cross bar in

the enclosure, which mounts next to the power

supply.Attach the Output Distribution Board to

the Adapter Bracket by aligning and sliding the

hanger brackets onto the bracket screws.

1. Loosen both screws enough to allow the

bracket prongs to slide over the screw

heads.

2. Firmly tighten only the bottom screw to

secure the module.

3.75”

95.25mm

J1 — Input connector

300 W output from unit

Input wire harness

(Alpha P/N 875-255-20)

J3 — 150W Output

Output wire harness

(Alpha P/N 875-262-20)

J2 — 150W Output

Output wire harness

(Alpha P/N 875-262-20)

NOTE:

The Output Distribution board is supplied with one interconnection cable (Alpha P/N 875-255-20), and

one output wire harness (Alpha P/N 875-262-20). The existing output wire harness is replaced by the

interconnection cable, and is transferred to one of the output connectors.