2 output distribution board (optional) – Alpha Technologies FlexNet ELPM 300-48D User Manual

Page 19

Advertising
background image

19

010-322-C0-003, Rev C

Electrical — General

Efficiency

> 90%

Grounding

Positive or negative terminal (user preference)

Startup Time

< 20s

Electrical — Input

Voltage, minimum

42Vdc

Voltage, nominal

48Vdc

Voltage, maximum

62Vdc

Electrical — Output I/II

Voltage, minimum

41 Vdc

Voltage, maximum

61Vdc

Current, nominal

3A

Output Ripple, max.

500mV RMS

Overcurrent/Short Circuit Protecting

Mode

Hiccup

Protection Trigger

<10ms

Threshold

4A

Environment

Operating Temperature

-40°C to +65°C (-40°F to +149°F)

Storage Temperature

-50°C to +70°C (-58°F to +158°F)

Solar Loading

Inclusive maximum operating temperature

Humidity

0-95%, Non-condensing

Altitude

Temp. spec applicable to 5,000ft (1524m). Above 5,000ft,

de-ratemax temp 2°C per additional 1,000ft (304.8m)

2.0

Specifications, continued

2.2 Output Distribution Board (optional)