Figure 4 — rectifier (or converter) report screen, 3 rectifier report from controller display, 4 analog input channels – Alpha Technologies Cordex HP CXRF 48-12kW User Manual

Page 18: 1 rectifier report for 12kw rectifiers

Advertising
background image

9400000-J0 Rev C

16

4.3.1 Rectifier Report for 12kW Rectifiers

The 12kW rectifier report contains three separate serial numbers. These serial numbers are derived from the top

level serial number located on the rectifier label. For example, if the label serial number is N300020/1210, then

the rectifier report screen displays three serial numbers 300021/1210, N300022/1210, and N300023/1210.

4.4 Analog Input Channels

The CXCM4 is equipped with analog input channels for voltage, current, and temperature.

Voltage Inputs

Two voltage input channels, V1 and V2, provide monitoring of discharge and charge voltage. The CXCM4 soft-

ware is pre-configured to monitor V1 for load voltage and V2 for battery voltage. V2 is used as the system refer-

ence for rectifier float voltage, low voltage disconnect (LVD), system high voltage alarm, and system low voltage

alarm.

Current Inputs

The CXCM4 software is pre-configured to monitor load current using an external 50 mV current shunt.

Temperature Inputs

Two temperature input channels, T1 and T2, monitor the battery temperature, and the room/ambient temperature,

and provide temperature compensation (temp comp). A voltage is supplied to these terminals to power the tem-

perature sensors.

Figure 4 — Rectifier (or Converter) report screen

Serial numbers of the modules

Select a module and then tap

View

Details

to produce a new window

with pull-down menus showing all of

the alarms and settings that are out of

tolerance

Report headings for serial number, current

display (% or A), number of alarms and set-

tings out of tolerance

A value of ‘---‘ indicates Comms Lost

FL + TC

54.00V

250A

Return to previous screen

4.3 Rectifier Report from Controller Display

To display the installed rectifiers and their status, logon through the controller interface.
From the

Main Menu

, select

Rectifiers >

Rectifier Report

to generate the report screen for all acquired modules in

the system (Figure 4). Tapping on a rectifier in the screen generates a

Rectifier Locate

command that causes the

rectifier's LEDs to flash briefly.

Advertising