Power module input, Environmental, Miscellaneous – Alpha Technologies Cordex HP CXRF 48-12kW User Manual

Page 46

Advertising
background image

Specifications for Alpha Switched Mode Rectifier Cordex 4kW

Alpha Technologies Ltd.

010-623-B1 Rev E

Printed in Canada. © 2012 Alpha Technologies Ltd. ALPHA and CORDEX are trademarks of Alpha Technologies Ltd. All Rights Reserved.

Page 2 of 3

Power Module Input

Voltage:

208, 220, 230, 240, 277 Vac nominal

Operational Range:

187 to 320 Vac

Extended Operation:

Low: 187 to 90 Vac (derated power)

Frequency:

45 to 66 Hz

Current:

17.5 A @ 240 Vac

21.5 A @ 208 Vac

23.5 A @ 176 Vac (maximum)

Recommended Feeder Breaker

Single Phase:

30 A, #10 AWG

Three Phase:

50 A, #6 AWG delta connection

30 A, #10 AWG wye connection

Power Factor:

> 0.99 at nominal conditions and 50-100% load

Protection:

10 kA-interrupting capacity fuses in active and neutral lines

Efficiency:

> 94% at nominal conditions and 25-75% load

> 92.5% at nominal conditions and 100% load

Inrush Current:

full load steady state current

Start-up Ready Time:

< 5 seconds (excluding soft start)

Start-up Delay:

120 seconds (programmable)

Soft Start:

10 seconds (user adjustable, not including start-up)

Input Transient Suppression:

Meets ANSI/IEEE C62.41 Category B3

Input Leakage Current:

< 3.5 mA @ 265 Vac 60 Hz

Environmental

Operating Temperature:

-40 to +75°C, power derated above 55°C (131°F)

(-40 to 167°F)

Storage Temperature:

-40 to +85°C

(-40 to 185°F)

Humidity:

0 to 95% non-condensing

Elevation:

-500 m to 2800 m; to 4000 m with temperature derated to 40°C

(-1640 feet to 9186 feet; to 13124 feet with temperature derated to 104°F)

Miscellaneous

MTBF:

> 479,000 hours ground benign @ 30°C (86°F)

Dimensions (in)

W3.4 x H6.3 x D13 (W3.4 x H7 x D13 including front panel)

Dimensions (mm)

W87 x H160 x D330 (W87 x H177 x D331 including front panel)

Advertising