Specifications for Alpha Switched Mode Rectifier Cordex 48-3.6kW Continued

Alpha Technologies Ltd.

010-600-B1 RevC

Printed in Canada. © 2012 Alpha Technologies Ltd. ALPHA and CORDEX are trademarks of Alpha Technologies Ltd. All Rights Reserved.

Page 2 of 3

Power Module Input

Voltage:

208, 220, 230, 240, 277Vac nominal

Operational Range:

176 to 320Vac

Extended Operation:

Low: 176 to 90Vac (derated power)

Frequency:

45 to 66Hz

Current:

16.8A @ 240Vac

19.4A @ 208Vac

22.8A @ 176Vac (maximum)

Recommended Feeder Breaker

Single Phase:

30A, #10AWG

Three Phase:

50A, #6AWG delta connection

30A, #10AWG wye connection

Power Factor:

>0.99 at nominal conditions and 50-100% load

Protection:

10kA-interrupting capacity fuses in active and neutral lines

Efficiency:

>92% at nominal conditions and 50-90% load

>91.5% at nominal conditions and 100% load

Inrush Current:

full load steady state current

Start-up Ready Time:

<5 seconds (excluding soft start)

Start-up Delay:

120 seconds (programmable)

Soft Start:

10 seconds (user adjustable, not including start-up)

Input Transient Suppression:

Meets ANSI/IEEE C62.41 Category B3

Input Leakage Current:

<3.5mA @ 265Vac 60Hz

Environmental

Operating Temperature:

-40 to +75°C, power derated above 65°C (149°F)

(-40 to 167°F)

Storage Temperature:

-40 to +85°C

(-40 to 185°F)

Humidity:

0 to 95% non-condensing

Elevation:

-500m to 2800m; to 4000m with temperature derated to 40°C

(-1640 feet to 9186 feet; to 13124 feet with temperature derated to 104°F)

Miscellaneous

MTBF:

>350,000 hours ground benign @ 30°C (86°F)

Dimensions (in)

W3.4 x H6.3 x D11.8 (W3.4 x H7 x D12.8 including front panel)

Dimensions (mm)

W87 x H160 x D300 (W87 x H177 x D326 including front panel)

Advertising