020-702-C0 Rev C WC

Page 5 of 16

Figure 4–Internal alarm card and CXCI I/O terminal block option

2.6 CXCM2 I/O Terminal Block (Option)

When using the DCP03 as a distribution solution for use with a 1.8kW rectifier shelf with a modular CXCM2

controller, an I/O terminal block can be installed in the UDC front door for front access to controller signals.
The CXCM2 terminal block kit comes with 25-pin, 15-pin, and 9-pin D-sub wire harnesses for connection to the

back of the 1.8kW rectifier shelf using the CXCM2 controller. Refer to the manual for the 1.8kW rectifier shelf (or

system).
The internal signals from the distribution center are wired to the CXCM2 I/O board direct from the internal alarm

board. The remaining relay outputs, digital inputs, and analog inputs are available on the board via terminal

blocks for customer connection of external signals. Refer to the customer connections (020–702–08) drawing at

the rear of this manual for details on terminal block assignments.

Figure 5–Internal alarm card and CXCM2 I/O terminal block option

2.7 4R/8D ADIO or 8R/8D 8DIO (Option)

The 4R/8D ADIO or 8R/8D 8DIO Cordex peripheral can also be installed on the front door of the DCP03. The

4R/8D ADIO option expands the I/O capability of an existing Cordex controller by adding an additional 4 relays

outputs and 8 digital inputs. The 8R/8D 8DIO option expands the I/O capability of an existing Cordex controller by

adding an additional 8 relays outputs and 8 digital inputs.
The 4R/8D ADIO or 8R/8D 8DIO peripheral installs on the right side of the front door. They connect to the Cordex

system via CAN communications using RJ-12 offset communications cables.
All I/O connections are made via screw terminal blocks. Refer to the customer connections (020–702–08) drawing

at the rear of this manual for details on terminal block assignments.

NOTE: The 4R/8D ADIO option and the 8R/8D 8DIO option cannot be used in the same configuration with the CXCM2

I/O terminal block assembly. For applications requiring CXCM2 and ADIO/ 8DIO, one of the two devices must be

mounted externally to the distribution center. Consult factory for options.

CXCM2 I/O

terminal block

assembly

DB-style cable

connections to

1.8kW shelf