5.5 CAN Serial Ports (4R/8D ADIO or 8R/8D 8ADIO Option)
Two CAN Serial ports (modular jacks with offset latches), for communications with Alpha’ Cordex rectifiers and
other CAN-enabled equipment (nodes) on the same system, are located on the optional 4R/8D ADIO or 8R/8D
8ADIO Cordex peripherals (Figure 10).
Daisy-chain from node to node (CAN OUT of one shelf to CAN IN of another) as necessary and ensure that only
the last shelf is terminated as follows:
5.5.1 CAN Termination
A CAN termination jumper is located beside the CAN ports. See the customer connections drawing for your shelf.
The CAN bus may be OPEN to the next node in the system or TERMINATED on the final node on the CAN bus.