6 system startup, 1 check system connections, 2 verify ac and power the rectifier shelf – Alpha Technologies DCP03 300A User Manual

Page 20: 3 check battery polarity and connect, 4 cxc reset, Ystem, Tartup, Check system connections, Verify ac and power the rectifier shelf, Check battery polarity and connect

Advertising
background image

020-702-C0 Rev C WC

Page 14 of 16

6

System Startup

Visually inspect the installation thoroughly.
After completing the system installation and power system wiring, perform the following startup and test

procedure to ensure proper operation:

6.1 Check System Connections

Ensure AC is off, battery is disconnected, and all power modules are removed from the shelf.

Triple-check the polarity of all connections.

6.2 Verify AC and Power the Rectifier Shelf

Install one power module.

Verify AC input voltage is correct and turn on the corresponding feeder breaker.

The power module OK LED should illuminate after a preset start delay.

Using the CXC, test functionality of various module alarms and controls.

6.3 Check Battery Polarity and Connect

Verify correct battery polarity using a voltmeter (ensuring no cells or batteries are reversed).

Connect battery as required to the output of the system.

Install remaining power modules.

In the adjustments menu of the CXC, set float and equalize voltage to the levels specified by the battery

manufacturer.

Using the CXC, test functionality of various module alarms and controls. In addition, perform a load test with

the system using a resistive load box as needed.

Enable the temperature compensation (temp comp) feature (Batteries menu) and program the settings for

slope and breakpoints (upper and lower) with respect to the specific batteries used.

6.4 CXC Reset

The reset button located on the front panel of the optional CXC is for restarting the microprocessor. When

pressed momentarily, the unit beeps twice then resets. The front-panel LEDs illuminate temporarily, but will

extinguish after the system has finished its 15-second self-test.
WARNING

Before removing a CXC from a live system, or performing controller maintenance, an external LVD

inhibit (or override) is required to avoid a disruption of service.
The LVD Control functions can be hardwired directly from the assigned relay output to an optional front panel LVD

override control.
Place the LVD Control switch to the INHIBIT position to keep the LVD contactor engaged.
WARNING

Do not leave the switch in the INHIBIT position. Doing so can result in a complete discharge of the

batteries during a power failure situation.
To allow the CXC to resume automatic control of the LVD contactor,

check that the AUTO IN (green) LED is lit

confirming that the CXC will keep the LVD contactor engaged. Then you can return the LVD Control switch to

the AUTO IN position.

Canada and USA toll free 24 hour emergency technical support: +1 888 462 7497.