19

4.0

Starting the Engine, continued

1

All battery voltage measurements are ± 1V

2

To enable forced output when the Overload Alarm LED is fl ashing, press the output button for at least 5
seconds. The Overload Alarm LED stops fl ashing. Release the output button, and then press it again for
at least fi ve seconds. The Output Indicator LED turns on steady, and power output begins. The operator
may then release the output button.

3

Engine shuts down after 1 second.

Table 4-1, Battery Voltage and Output Indications

NOTE:

To manually disconnect the Output Voltage, press the OUTPUT SW momentarily to remove voltage from the
battery pack. See Step 1 of Section 5.0, Engine Shutdown and Cable Removal.

To re-establish output voltage after manual or automatic disconnection, turn the ENGINE SW counter-
clockwise to OFF. After the engine stops, turn the ENGINE SW to ON and follow the procedures in Section
4.0, Starting the Engine.

Not Available

Not Available

Battery Voltage

0V to 2V

2V to 27V

27V to 42V

42V to 55V

>56V

Voltage Select

Switch Position

Output Indicator

(Green LED)

Overload Alarm

(Red LED)

Forced Output

36V

48V

36V

48V

36V

48V

36V

48V

36V

48V

OFF

OFF

OFF

OFF

ON

OFF

OFF

ON

OFF

OFF

OFF

OFF

FLASHING

FLASHING

OFF

FLASHING

FLASHING

OFF

FLASHING

FLASHING

ENABLED

ENABLED

ENABLED

2

1

3

3

Not Available

Not Available

Not Available

Not Available

Not Available