Page 23

Advertising
background image

23

031-161-B0-006, Rev. F

2.0 Installation,

continued

2.2

Ground-mount Installation: PWE-4, PWE-8, PWE-9, PWE-D36, continued

2.2.2 Enclosure Grounding: Ground-mount

Fig. 2-5, Suggested Grounding Method

Alpha generally recommends using the grounding method illustrated below. However, the grounding
method appropriate for a particular site depends on local codes, the NEC (National Electric Code), and
other site-specifi c characteristics.

Alpha Technologies recommends 5 ohms minimum ground resistance between enclosure and ground
rods, in accordance with IEEE 1100-1999 Powering and Grounding Electronic Equipment.

Alpha Technologies assumes no responsibility or liability for failure of the installer to comply with the
requirements of all applicable local and national codes. Where allowed, exothermic welding may be used
as an alternative to Burndy clamps and connectors.

NOTE:

Corrosion-proof, twenty-fi ve-year connections suitable for direct burial must be used.

CAUTION!

Service Grounding (required)

#6 bare copper wire from service entrance ground bar, with two 1/2" X 8' (12.7mm x 2.4m) copper

ground rods, driven at least six feet (1.8 meters) apart.

Lightning Protection (optional)

Four 1/2" X 8' (12.7mm x 2.4m) copper ground rods, driven at least two feet from pad.

#6 bare copper wire loop, at least 30" (762mm) below grade, and terminated at each ground rod.

#6 bare copper wire from loop to enclosure ground bar in service entrance.

1

2

3

4

4

1

2

2' min.

2

2

2

Burndy YGHP58C2W-3 or Equivalent

Burndy YGHP58C2W-2TN or Equivalent

Terminate at Service Entrance Ground Bar

Terminate at Enclosure Ground Bar

3

8' (2.4m) Ground Rods
6’ (1.8m) Apart (min.)

#2 AWG

2' (0.6m)

min.