031-161-B0-006, Rev. F

36

Disconnect all power sources from the SPI (Service Power Inserter) before removing its
cover. Verify that the SPI is disconnected from both the utility power and the power supply
before beginning procedure.

WARNING!

Fig. 2-20, SPI Locations

PME Enclosures

SPI

Power Suppy Output
(Coaxial Cable)

PWE Enclosures

SPI

Power Suppy Output
(Coaxial Cable)

Procedure:

1. Disconnect the SPI from all power sources.

2. Remove the two screws securing the cover to the SPI chassis.

Remove the cover, exposing the circuit board and seizure
screw assembly.

SPI Cover

Seizure Screw
Assembly

3. Screw the Coaxial Termination into Output Port on bottom of SPI, inserting the stinger

into the seizure screw assembly.

4. Tighten seizure screw to 35 in-lbs.

5. Replace SPI cover and reinstall screws.

6. Verify switch on top of SPI is on the ON position.

Fig. 2-21, SPI

Fig. 2-22, SPI (side view)

Seizure Screw

Stinger

Coaxial

Termination

Output Port

To prevent arcing and failure of the unit, insert the coaxial cable completely into the seizure screw
assembly and tightened the seizure screw to 35 inch-pounds.

CAUTION!

2.0 Installation,

continued

2.4

Connecting the Coaxial Cable, continued

2.4.2 Connecting the Service Power Inserter (SPI)