6 installing the xm series 2 power supply, 0 installation, continued – Alpha Technologies PME Series User Manual

Page 47

Advertising
background image

47

031-161-B0-006, Rev. F

4. After verifying that the batteries, battery connections, and battery cables are connected

properly, plug the battery cable connector from the battery string or BIT into the power
supply’s BATTERY INPUT connector. The connector is keyed and color-coded to fi t in
only one direction. See Fig. 2-32.

5. Plug the Remote Temperature Sensor into the TEMP PROBE connector located on the

Inverter Module assembly on the front of the power supply. See Fig. 2-32.

6. If applicable, plug the optional Local/Remote Indicator lamp (LRI) cable into the LRI

connector. See Fig. 2-32.

7. If you are installing a Tamper Switch (TMPR SW), plug it into the 2-pin TMPR connector,

and plug the transponder cable into the transponder TMPR connection. See Fig. 2-32.

8. Plug the connector from the SPI into the power supply’s OUTPUT 1A. If the enclosure

has the optional AC Indicator (ACI) lamp, plug the connector from the SPI into the ACI
and the connector from the lamp into the power supply’s OUTPUT 1A. If the PIM option is
installed, connect a second SPI to OUTPUT 2. Make sure that the SPIs “ALT/ON” switch
is in the ON position. See Fig. 2-32.

9. If the installation includes a Module Retaining Cable option, attach the end of the cable to

the hole provided at the top, rear, center of the enclosure. Thread the cable through the
power supply handle and clip it back on itself.

10. The installation is complete. Do Not apply AC power to the power supply or switch

the Inverter Module’s BATTERY BREAKER ON. Refer to the power supply Operator’s
Manual for Start-up and Test procedures.

2.0 Installation,

continued

2.6 Installing the XM Series 2 Power Supply

Installation Procedure:

1. Before installation, inspect the power supply for damage or loose connectors.

2. Place the XM Series 2 Power Supply in the lower-right compartment of PME enclosures,

or the upper-right compartment of PWE enclosures.

3. Switch the BATTERY BREAKER on the front of the power supply OFF. This prevents the

inverter from starting when the batteries are fi rst connected to the power supply. See Fig.
2-32.

Check the polarity and voltage of the battery cable connector with a voltmeter before proceeding.
Connecting the battery string or strings to the power supply with incorrect polarity may cause a
short-circuit, and possible equipment damage. Check all battery connections for proper installation.
For complete battery installation procedures, see the “Battery Installation” section in this manual.

CAUTION!

OUTPUT 2

OUTPUT 1A

LRI

Battery

Input

Temp
Probe

Battery

Breaker

OUTPUT 1B

N+1

N+1

6

8

3

4

5

7

Fig. 2-33, XM Series 2 Power Supply

Advertising
This manual is related to the following products: