1. Battery Installation and Wiring Diagram

Battery Cable Kit, Precision Temperature Sensor / Smart AlphaGuard or Battery Sense Harness

Smart AlphaGuard (Embedded) — use Battery Harness, p/n 875-848-20,

(2 battery strings) — use p/n 875-848-21,

(3 battery strings) — use p/n 875-848-22,

(4 battery strings) — use p/n 875-848-23.

Re-use existing External Alphaguard Battery Sense Harness by installing a retrofit kit.

External AlphaGuard Battery Sense

Harness to Smart AlphaGuard (1 battery string) — use retrofit cable p/n 875-910-20,

(2 battery strings) — use p/n 875-910-21,

(3 battery strings) — use p/n 875-910-22,

(4 battery strings) — use p/n 875-910-23.

Precision Temperature Sensor (PTS), p/n 746-331-20

CAUTION!

Use 1/4-20 x 3/4” (19mm) bolts for threaded insert terminals. If using a spacer for the in-line fuse link, use 1/4-20 x

1” (25.4mm) bolts.

3/4" (19mm) x

1/4-20 Bolt

Split Washer
Flat Washer

Battery Sense Cable

or RTS

Battery Cable
Battery Terminal

Nut

Split Washer
Flat Washer

Battery

Cable
In-Line Fuse Link

Flat Washer
1" (25.4mm) or

3/4" (19mm) x

1/4-20 Bolt

1" (25.4mm) x

1/4-20 Bolt

Flat Washer

Split Washer

Spacer
Battery

Terminal

Fuse

Load batteries into cabinet with the positive terminals (+) facing forward.

Torque all nuts and bolts to 110 in-lbs. (12.43N-m)

Vbatt 3A

36V

Red, Pin 9

3A

2A

1A

A/B/C/D NEG Black, Pin 5

Vbatt 2A

24V

Orange, Pin 4

Vbatt 1A

12V

Brown, Pin 10

To Power Supply

Black (String -) 0V

Red

PTS

3

3

1

11

11

3A

POS(+)

NEG(-)

NEG(-)

NEG(-)

POS(+)

POS(+)

36VDC

2A

1A

Threaded Insert Terminals

The compatibility of the XM3 SAG system with certain vaults is dictated by the length of the SAG harness. Contact

your local sales representative for more information.

NOTE:

Advertising