3. DOCSIS Communications Module

1. Connect the Battery Sense Harness to the A/B or C/D Connector (6). For XM3 units with the Smart AlphaGuard

(SAG) option, connect the Battery Harness to the SAG Connector (11) located on the left side of the XM3 Power

Supply.

2. Connect Tamper Switch Wire Harness to the TPR Connector (8).
3. Connect the RF drop to the RF Connector (7).

Front Panel Connections

To Battery Sense

Harnesses

TPR Connector

Required

Grounded Surge Protector

(Alpha p/n 162-028-10 or equivalent)

RF Cable

to Headend

RF Drop

7

8

6

Some systems may require reconfiguring the output voltage setting. If necessary, follow the steps below to complete the

procedure. If the factory default satisfies your system requirements, proceed to Section 3.

2. Output Voltage Reconfiguration Procedure

Alpha DOCSIS Transponder (1 battery string) — use Battery Sense Harness, p/n 874-842-21.

Alpha DOCSIS Transponder (2 battery strings) — use Battery Sense Harness, p/n 874-842-28.

AlphaGuard (external) — use Battery Sense Harness, p/n 875-510-20 (S9) or p/n 875-510-21 (D9).

6

The output voltage factory default is 89 Volts.

NOTE:

The DOCSIS specification for downstream power level is 0 dBmV, +/- 15 dBmV. The upstream power level should not

exceed +50 dBmV.

NOTE:

Tools Required:
Small flat-blade screwdriver.

1. To access output voltage terminal, remove the Inverter Module.

2. Loosen the terminal screw and move the output voltage wire (Fig. 1)

to the desired output voltage position on the terminal strip.

3. Torque the terminal block screw to 7 in-lbs. (0.79N-m) to secure the

output voltage wire.

4. Replace the Inverter Module.

Fig. 1 - Output voltage wire and terminal bar.