Power module configuration, Installation procedure, Caution – Alpha Technologies XM3-HP Series - Quick Start Guide User Manual

Page 4

Advertising
background image

1. After wiring battery cable kit, battery sense cables and PTS, as shown in

Section 1, verify DC breaker is OFF.

2. Connect the Smart AlphaGuard (SAG) wire harness to SAG port (11). If no

SAG is installed, connect battery sense harness to the transponder (6).

3. Connect PTS to the PTS connector (3).
4. Connect the RF cable and the tamper switch to the transponder.
5. Verify the SPI / ALT Box Switch is in the ALT position.
6. Connect the SPI / ALT Box input cable to the Output 1 Connector (9). If 2nd

SPI / ALT Box is present connect input cable to Output 2 Connector.

7. Connect the LRI to the XM3. For existing LRI installations, use LRI adapter

kit, p/n 875-952-20.

8. Turn ON AC breaker and verify it is the correct utility voltage at the outlet (per

unit’s nameplate voltage). If correct, plug in the line cord into the utility outlet.

9. Verify correct battery voltage and polarity on battery cable connector with a

digital voltmeter, if correct plug into Inverter Module (1).

10. Turn battery breaker ON.
11. Verify no alarms are present after power up initialization. Wait for alarms to

clear (approximately 60 seconds).

12. If no alarms are present, proceed to Step 16.
13. If alarms are present and do not clear after 60 seconds, press the softkey with

ALM (C) to see the ACTIVE ALARM list for the menu item.

14. Press UP (

) or DOWN () to select the alarm of interest.

15. Press ENTR to select the alarm and display diagnostic information. Press

ESC to return to the alarm list.

16. On the SmartDisplay, press the BATT softkey, enter the BATT CONFIG

menu and select BATT MODEL and NUM BATT STRINGS (Fig. 2).

17. On the SmartDisplay, press BATT softkey, enter BATT CONFIG, enter BATT

MHOs* and DATE Code (Fig. 3).

*Note: Battery MHOs and Date code can only be set after DOCSIS

transponder has registered with CMTS. Please wait 3 minutes after

power up to enter Battery MHOs measurements.

18. Switch SPI / ALT Box Switch to ON, verifying the load on the XM3.
19. Perform a self-test by pressing and holding the Test Button (H) for 1-2

seconds. Wait for self-test completion before proceeding.

20. Perform standby test by shutting OFF utility breaker and verifying it goes into

STANDY MODE and supports the load.

21. Reapply AC power and verify the unit transfers to LINE MODE.

Installation Procedure

4. Power Module Configuration

XM3-918HP

90V/10.0A

OPERATION NORMAL

OK

ALM

OK

OK

PWR

BATT

COMM

APPS

Indicates

Model

and

Output Voltage/Current

Softkeys (Menu driven

system configuration)

A

A

B

Describes

Power Supply

Mode of Operation

Describes

Status of Functions

C

E

E

C

D

Functionality top level menu

PWR, BATT, COMM and APPS

D

B

EDIT USING

hi 8

<ESC>

BATT MODEL

OTHER

ENTR

h

i

ESC

BATT

A1

DATE

1/10

hi

ADJUST VALUE

ENTR to shift field
ENTR

h

i

ESC

Fig. 2 - Battery Model input

Fig. 3 - Battery DATE Code and MHOs input

BATT

A1

MHOs

1000M

hi

ADJUST VALUE

ENTR to save
ENTR

h

i

ESC

CAUTION!

Before applying power, verify power supply rating is matched to AC input utility. Verify a low-resistance ground is

installed in accordance with the NEC (refer to CableUPS Power Supply technical manual for details).

XM3-918HP

90V/0.4A

**ACTIVE ALARM**

OK

PWR

PM

BATT

ALM

COMM

OK

APPS

G

H

OUTPUT LED (green)

SOLID = Operation Normal
FLASHING = Minor Alarm
OFF = Major Alarm

ALARM LED (red)

FLASHING = Major Alarm
OFF = Minor Alarm
OFF = Operation Normal

G

H

I

I

SELF TEST BUTTON

Press button to initiate self test.