1 setting end stop closed, 2 setting end stop open, 3 setting limit switchingclosed – AUMA Electric part-turn actuators SG 05.1 - 12.1_SGR 05.1 - 12.1 NORM User Manual

Page 12: End stops 12, Sg on butterfly valves 12, Limit and torque switches, Fitting the cover, Setting end stop closed

Advertising
background image

8.

Setting the end stops for part-turn actuators on butterfly valves

For actuators on ball valves refer to page 13, section 9.

The settings can only be performed if the valve has not yet been mounted in a

pipeline.

.

If part-turn actuators are supplied without a valve:
hex. bolts (03, figure E) are not tightened.

.

If part-turn actuators are supplied with a valve:
hex. bolts (03, figure E) are tightened.
End stops and limit switching should have already been set
and only have to be c
hecked.

8.1

Setting end stop CLOSED

.

If hex. bolts (03, figure E) are tightened:

loosen by approx. 3 turns.

.

Turn handwheel clockwise (closing direction), until valve is closed

(end position CLOSED).

Check whether end stop (10) has rotated, otherwise turn end stop (10) clock-

wise up to the stop.

.

In case end position CLOSED has been passed:

reverse several turns at the handwheel and approach end position again.

.

Turn end stop (10) by 1/8 turn counterclockwise

(Protective cap (16) must not be loosened in the process.).

The end stops are designed for the protection of the valve.
They have to be set as to ensure that they are not used during
normal operation.

.

Fasten hex. bolts (03) crosswise with torque 18.4 ft lbs.

8.2

Setting end stop OPEN

The swing angle has been set in the factory. Therefore, the end stop OPEN

need not be set.

8.3

Setting limit switching
CLOSED

After setting the end stop CLOSED, the limit switching for end position CLOSED

can be set immediately (page 16, section 13.12.). For this, the switch compart-

ment has to be opened and the indicator disc has to be removed (refer to page

15, section 11.).

12

Part-turn actuators SG 05.1 – SG 12.1 / SGR 05.1 – SGR 12.1
AUMA NORM

Operation instructions

16

10

03

Figure E: Setting end stop CLOSED

Advertising