Setting the operating time

For part-turn actuators with 1-phase AC motors, the operating time can be

adjusted.

Work on the electrical system or equipment must only be carried
out by a skilled electrician himself or by specially instructed
personnel under the control and supervision of such an electrician
and in accordance with the applicable electrical engineering rules.

.

Remove motor cover (figure R).

.

Set required operating time with potentiometer (figure S).

.

Clean sealing faces of housing and motor cover.

.

Check whether O-ring is in good condition.

.

Apply a thin film of non-acidic grease to the sealing faces.

.

Fit and fasten motor cover.

(For enclosure protection IP 68, the motor cover is additionally sealed with

thread sealing material.)

Check the part-turn actuator for damage to paint finish. If damage
to paint-finish has occurred after mounting, it has to be touched
up to avoid corrosion.

Part-turn actuators SG 05.1 – SG 12.1 / SGR 05.1 – SGR 12.1

Operation instructions

AUMA NORM

25

Figure R: Part-turn actuator with 1-phase AC motor

Motor cover

STELLZEIT

OPERATING TIME

Z 026.161

Figure S: Setting the operating time

Operating time

potentiometer

SG 05.1

5.6 to 45 seconds

SG 07.1

11 to 90 seconds

SG 10.1

11 to 90 seconds

SG 12.1

22 to 180 seconds

Table 6: Operating times for 90°