Enclosure protection ip 68 (option), Enclosure protection ip 68 26 – AUMA Electric part-turn actuators SG 05.1 - 12.1_SGR 05.1 - 12.1 NORM User Manual

Page 26

Advertising
background image

21.

Enclosure protection IP 68 (option)

Definition

According to EN 60 259, the conditions for meeting the requirements of enclo-

sure protection IP 68 are to be agreed between manufacturer and user.

AUMA actuators and controls in enclosure protection IP 68 meet the following

requirements according to AUMA:

.

Duration of submersion in water max. 72 hours

.

Head of water max. 6 m

.

Up to 10 operations during submersion

.

Modulating duty is not possible during submersion

Enclosure protection IP 68 refers to the interior of the actuators (motor, gearing,

switch compartment, controls, and terminal compartment).

Inspection

AUMA actuators and controls in enclosure protection IP 68 undergo a routine

testing for tightness in the factory.

Cable glands

.

For the entries of the motor and control cables, appropriate cable glands in

enclosure protection IP 68 must be used. The size of the cable glands must be

suitable for the outside diameter of the cables, refer to recommendations of

the cable gland manufacturers.

.

As standard, actuators and controls are delivered without cable glands. For

delivery, the threads are sealed with plugs in the factory.

.

When ordered, cable glands can also be supplied by AUMA at an additional

charge. For this, it is necessary to state the outside diameter of the cables.

.

The cable glands must be sealed against the housing at the thread with an

O-ring.

.

It is recommended to additionally apply a liquid sealing material (Loctite or

similar).

Commissioning

When commissioning, the following should be observed:

.

Sealing faces of housing and covers must be clean

.

O-rings of the covers must not be damaged

.

A thin film of non-acidic grease should be applied to sealing faces

.

Covers should be tightened evenly and firmly

After submersion

.

Check actuator.

.

In case of ingress of water, dry actuator correctly and check for proper func-

tion.

26

Part-turn actuators SG 05.1 – SG 12.1 / SGR 05.1 – SGR 12.1
AUMA NORM

Operation instructions