4 displaying the appliance history, 5 display the selected appliance, 6 setting the pump on/off – A.O. Smith BFC - 28 User Manual

Page 66: 7 setting the service interval, Displaying the appliance history, Display the selected appliance, Setting the pump on/off, Setting the service interval

Advertising
background image

Service program

66

Instruction Manual BFC

9

is

Figure 9.3

shows an example of ‘Blocking errors’. In this case, the text

HISTORIE OF ERRORS

is followed by

(B)

.

Figure 9.4

shows an example of the ‘Lock out errors’. In this case, the text

HISTORIE OF ERRORS

is followed by

(L)

.

n

Remark

For an overview of all errors and the possible causes, please refer to chapter

’10 Troubleshooting’

.

9.4

Displaying the
appliance history

The appliance history sub-menu is used to display the burning hours, the
number of ignitions, the number of flame errors, and the number of ignition
errors.
Bring up the menu for displaying the appliance history via:

S:

APPLIANCE HISTORY

Figure 9.5

shows an example.

9.5

Display the selected
appliance

Bring up the menu for displaying the appliance selection via:

S:

SELECT APPLIANCE

The appliance selection has been correctly preset in the factory.

Figure 9.6

shows the relevant display.

9.6

Setting the pump
on/off

If a program-controlled pump is installed (Installation, see paragraph

3.10.6

)

then this can be turned ON or OFF via:

S:

PUMP RELAY

The standard setting for the pump relay is OFF.

Figure 9.7

shows the related display.

If the mode

WEEK PROGRAM

or

EXTRA PERIOD

is active, then the setting for

mode

WEEK PROGRAM

or

EXTRA PERIOD

has priority over the ON/OFF

selection for the pump relay in the service menu.

Example

One of the week program periods is currently active. The pump relay setting is
OFF within this period. If the pump relay is set ON in the service menu, the pump
will nonetheless remain OFF. The pump will only switch ON once the week
program period has ended.

9.7

Setting the service
interval

To aid servicing, the ThermoControl has a service interval which defines the
frequency of maintenance by the service and maintenance engineer based on
the number of burning hours. Refer also to paragraph

11.2

.

HISTORIE OF ERRORS(B)

S04 SENSOR ERROR

F06 IONIZATION

È CO2 50 HZ ERROR

Figure 9.3 Blocking errors

HISTORIE OF ERRORS(L)

F02: FAN

F07: FLAME ERROR

È ...

Figure 9.4 Lock out errors

APPLIANCE HISTORY

BURNINGHOURS 000410

^IGNITIONS

001000

ÈFLAME ERRORS 000021

IGNIT ERROR

000013

Figure 9.5 service program

SELECT APPLIANCE

»ADM 40 - 135

^ ADMR 40 - 135

È BFC 28

BFC 30

BFC 50

BFC 60

BFC 80

BFC 100

Figure 9.6 Select appliance

PUMP RELAY

»ON

OFF

Figure 9.7 Pump relay