Pressure differential alarm option – ClimaCool IOM AR2 SERIES User Manual

Page 25

Advertising
background image

23

www.climacoolcorp.com

®

Description:

The pressure differential alarm option continually monitors

and displays the strainer’s inlet and outlet differential

pressure . When the strainer element (conical strainer basket)

becomes significantly clogged, the pressure differential

switch-gauge will trigger an audible siren and a visual

flashing alarm light . These alarms are intended to alert

maintenance personnel that the strainer element must be

removed and cleaned (see page 18 for complete strainer

element cleaning instructions) .

Operation Instructions:

Remove the power supply and insert the connector end into

the socket on the bottom of the PDA housing, as indicated

in the drawing above . Plug the transformer into the power

source . Standard systems are supplied with a 120V power

supply to the primary of the transformer, with an output,

secondary of 12 VDC .

The pressure differential switch-gauge is factory set to

7-8 PSI . The ClimaCool Strainer operates at a pressure

differential slightly less than 1 PSI during maximum flow

when the strainer screen is clean . By the time this differential

pressure reaches 7-8 PSI, the strainer element will be

significantly clogged and require immediate removal and

cleaning .

To adjust the pressure differential switch-gauge setting, insert

a 1/16” allen wrench and rotate the differential set-point

contact to the desired location (see Fig . 1) .

Note: We do not recommend setting the differential

switch-gauge higher than 10 PSI. Disabling the alarm

or increasing the alarm set point could result in damage

to the strainer element and allow debris to pass into the

system.

PSID High

PSID Low

Pressure Differential Alarm (PDA) option

Alarm Reset Button

FRONT

VIEW

LEFT SIDE

VIEW

Power To ATF

110 Volt/12 Volt DC

Wall Transformer

Visual

Alarm

Audible

Alarm

Pressure Differential

Switch-Gauge

LED Power Indicator

Differential

Set-Point Contact

Cover-Plate Screw (4) in Corners of

Box (DO NOT REMOVE).

Visual

Alarm

RIGHT SIDE

VIEW

TOP

VIEW

BOTTOM

VIEW

AUX Contacts

(On or Off with Alarm)

Red & Black

Cable Retainer

Pressure Differential Alarm Option