REFRIGERATION SYSTEM REPROCESSING

All ClimaCool remote air-cooled modular chillers leave the

factory with both refrigeration circuits pressurized with 50 psig of

dry nitrogen . These split system chillers require interconnecting

refrigeration piping between the ClimaCool AR2 compressor/

evaporator module section and the remote condenser section .

The condenser section provided by ClimaCool is typically a

remote air-cooled condenser configuration . Contact the factory

for guidelines for customer supplied, field integration to other

permissible condenser types, such as evaporative condenser

configurations . The refrigerant charge will be weighed-in in the

field based on the condenser configuration and condenser model .

The ClimaCool AR2-25 and AR2-30 models are equipped with

a 72 pound liquid receiver capacity per compressor circuit . The

AR2- 50 and AR2-65 models have an 84 pound liquid receiver

installed per circuit . The installing contractor MUST make the

determination of refrigerant type to be charged in the field . All

ClimaCool AR2 module systems can be charged with either

refrigerant R-22 or R-407C . Field installation of additional

receiver capacity may be required depending on the refrigerant

retaining volume of the remote condenser and interconnecting

piping . After the total refrigerant amount is charged into each

circuit (weighed in using an appropriate refrigeration scale at

+/- 2 pound accuracy), the resultant weight should be recorded

on the AR2 module data plate for future reference . See “System

Refrigerant Charging” section for specific charging guidelines .

AR2 Module Refrigeration Piping Connections

The discharge and liquid line stub-out connections at the AR2

module section are equipped with shut-off valves with capped

leads . Never uncap these leads without checking the shutoff

valves to be sure that they are fully closed and the units are ready

for piping . All scroll compressors in ClimaCool AR2 modules are

equipped with POE refrigeration oil . Systems with compressors

using POE oils must be kept closed at all times except when the

interconnecting piping is being directly installed . POE oils are

extremely hydroscopic in nature and will absorb an undesirable

amount of moisture from normal ambient air within a few

minutes .

Copper Tubing, Brazing and System Reprocessing

Recommendations

Copper tubing must be refrigeration grade (ACR type “L”) .

Be sure to install appropriate copper fittings rated for ACR

applications . Never leave refrigerant lines open when they are

not directly being installed . Never rely on the last refrigerant

connection joint at a specific section (AR2 module or condenser

section) to provide structural support for the interconnecting

piping . Line pulsation may occur at start-up and shut down of

scroll compressors . Additional line support may be required to

prevent vibration transmission or movement in the line . Ensure

that all interconnecting piping is properly and independently

braced at 7’ minimum intervals, and within 2’ from each section’s

final connection location, to prevent joint fracture due to line

vibrations or liquid hammering .

Use 15% silver-phosphorus braze filler rod when brazing copper-

to-copper joints, . When brazing copper-to-brass joints, apply

“sta-silv” brazing paste (or equivalent) sparingly to the joint

areas, and use 45% silver-phosphorus braze filler rod . Always

purge a generous flow of dry nitrogen (approx . 10 CFH) through

the lines while brazing to prevent internal scaling of copper oxide

on heated copper surfaces exposed to air .

When sizing the interconnecting refrigerant lines, never use the

stub-out sizes at the AR2 module section as your determining

factor . For proper operation, all discharge and liquid lines must

be sized in accordance with the recommendations provided in

the following piping sections . After installing the interconnecting

piping, proper system evacuation and reprocessing guidelines

are provided in the section titled, “Refrigeration System

Reprocessing” .

Liquid Line Piping Recommendations

All liquid lines should be kept as short as possible, and the line

sizing is determined to provide for a low-pressure drop to prevent

liquid line flashing . There should always be a gradual negative

elevation change when traversing from the remote condenser

location to the AR2 module section . Avoid any reversing

elevation changes throughout this liquid line run . Horizontal

liquid lines should be sloped downward in the direction of

refrigerant flow at a pitch of 1/8” per foot . The total equivalent

distance between the condenser and the AR2 section (including

allowances for U-bends and 90o elbows) should not exceed 100

feet . Avoid routing liquid lines through heated spaces which may

result in undesirable flash gas generated at the TXV inlet . Avoid

insulating liquid lines .